Technical data

5 Operation
5.1 Introduction
This chapter describes the operating characteristics of the SP40S Multi-Function Facility
Communication System. Included is information about the following panel features:
Supervision
Audio Notification Appliance Output Circuit Supervision
Amplifier Supervision
Actions that Initiate Alarms
5.2 User Interface
The User Interface on the SP40S displays the basic status of the unit as well as providing a
limited number of user controls. The User Interface includes a Microphone and the manual
activation or recording of the eight messages. There is also a button to silence the audible trouble
indicator. Status indicators include POWER ON, SYSTEM TROUBLE, AC TROUBLE,
ALARM ACTIVE, and STROBE ACTIVE (see Figure 3-3).
5.3 Supervision
A SYSTEM TROUBLE LED indicates that the supervisory functions have detected a
malfunction in the panel. When a trouble condition is detected, the panel may not be able to
receive and/or broadcast messages from the control panel.
If a trouble condition is detected by any of the supervisory functions, the internal sounder
operates the panel Form C TROUBLE relay (normally energized), changes state, and the yellow
SYSTEM TROUBLE LED turns “ON.” The Trouble Status Relay (TB2) must be properly
connected to and used by the control panel to indicate a system trouble. At the same time, one of
the yellow trouble location LEDs identifies the location of the trouble condition. The internal
sounder can be silenced for 20 hours by depressing the “Trouble Acknowledge” Switch (SW1, on
the User Interface). Any subsequent troubles cause the sounder to be re-activated. If a trouble
condition is indicated, follow the procedures in Chapter 8 "Troubleshooting.”
An AC Loss can be selected to be reported as a system trouble after 170 minutes (SW2-Position 2
= ON). This is desirable for off-premise trouble reporting. If SW2-Position 2 is OFF, AC Loss is
reported as a system trouble after 30 seconds.
SP40S Multi-Function Facility Communication System Manual, Revision D
1