Technical data
Chapter 4: Installation
+
-
+
-
AUDIO
STROBE
UL LISTED 10K OHM, 1/2 W
END OF LINE RESISTOR
UL LISTED 10K OHM, 1/2 W
END OF LINE RESISTOR
Figure 4-9 Wiring Diagram for Combination Audio/
Visual Notification Appliances
CAUTION: Do not loop wire under terminals. Break wire run to provide supervision of the
connection.
+
-
AUDIO
UL LISTED 10K OHM, 1/2 W
END OF LINE RESISTOR
Figure 4-10 Wiring Diagram for Audio Only Notification Appliance Output
CAUTION: Do not loop wire under terminals. Break wire run to provide supervision of the
connection.
4.5.7 Wiring the Alarm Output Contact
The location of the Alarm Output Connections (TB1) is shown in Figure 4-1. A magnified view of this area on
the motherboard is shown in Figure 4-11.
• Wire gauge selection of the Alarm Status output contact wiring involves consideration of all factors
including, wire loop length, maximum current capacity, and maximum voltage drop allowable.
• The Alarm Status output contact is Form C, rated for 2.0 amps at 24VDC, resistive load.
• For terminal connection details of the Alarm Status output contact (shown in the non-alarm mode), see
Figure 4-11.
• Contacts are duplicated for ease of IN and OUT wiring.
• An external 24VDC or the internal 24VDC connection (TB1) can be used to power non-supervised
Alarm appliances.
SP40S Multi-Function Facility Communication System Manual, Revision D
17