Technical data
Chapter 3: Overview
SW4 (Tone Types)
PIN FUNCTION ON
1 Tone Type - DV1 Code 3 (OFF = continuous)
2 Tone Type - DV2 Code 3 (OFF = continuous)
3 Tone Type - DV3 Code 3 (OFF = continuous)
4 Tone Type - DV4 Code 3 (OFF = continuous)
5 Tone Type - DV5 Code 3 (OFF = continuous)
6 Tone Type - DV6 Code 3 (OFF = continuous)
7 Tone Type - DV7 Code 3 (OFF = continuous)
8 Tone Type - DV8 Code 3 (OFF = continuous)
9 Backup tone Code3 (OFF = slow whoop)
10 unused --
SW5 (Pre-tone/Post-tone Enable)
PIN FUNCTION ON
1 Pre-tone - DV1 Pre-tone ON for Message 1
2 Pre-tone - DV2 Pre-tone ON for Message 2
3 Pre-tone - DV3 Pre-tone ON for Message 3
4 Pre-tone - DV4 Pre-tone ON for Message 4
5 Pre-tone - DV5 Pre-tone ON for Message 5
6 Pre-tone - DV6 Pre-tone ON for Message 6
7 Pre-tone - DV7 Pre-tone ON for Message 7
8 Pre-tone - DV8 Pre-tone ON for Message 8
9 Post-tone - All Post-tones enabled (Post-tone Matches Pre-tone)
10 Message Repeat ON = Message plays a minimum of 3 times
OFF = Message plays a minimum of 1 time*
*NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTIONS AND OTHER INVOLVED
PARTIES: In order for this product to comply with the requirements in the Standard for Control Units and Accessories for
Fire Alarm Systems, UL 864, Position 10 of SW5 must be kept in the ON position. UL 864, 9
th
Edition, section 34.2.1.1
requires the alert tone/prerecorded message combination shall be repeated a minimum of 3 times.
SP40S Multi-Function Facility Communication System Manual, Revision D
15