Technical data
Chapter 10: Module Descriptions  
Series SPB Audio Boosters Manual, Revision A 
9-2
9.3 Electrical 
9.3.1 Input 
Parameter  SPB-80/4 and SPB-160  SPB-320 
Input Voltage  120VAC, 3.8A, 50-60 Hz  120VAC, 7.4A, 50-60 Hz 
Battery Backup  24VDC, Up to 33Ah  24VDC, Up to 33Ah 
9.3.2 Battery Current Calculations 
The current draw of the Series SPB Audio Booster is determined by the configuration being 
utilized. Section 4.8, Battery Care and Batteries Calculation, will assist you in developing the 
current requirements. 
9.3.3 Activation Inputs 
The panel audio output is activated by applying a 1V, 25V, or 70.7V to AUD IN. Power 
consumption is 1.2 Watts @ 70.7V and 0.25 Watts @ 25V. 
The AUX IN is triggered using 8 – 33VDC at 10mA in NAC mode or with contact closure in CC 
mode. 
9.3.4 Outputs 
Parameter  Description 
Visual Notification Appliance Output 
(SPB-80/4 only) 
2 output circuits. 2.0 amps at 24VDC. 
Supervised. 
Central Amplified Audio Output  (SPB-80/4) 1 output circuit. 
Selectable 25 or 70.7 Volt output at 80W max. 
Supervised. 
(SPB-160) 2 output circuits. 
(SPB-320) Selectable 25 or 70.7 Volt output at 
80W max for each. Supervised. 
Trouble Contact  Form C contact normally energized. Contacts 
transfer during trouble: 1.0 amps at 24VDC 
max, resistive load (see following warning). 
Non-Supervised. 
 WARNING:  Do  not  exceed  the  ratings  of  the  status  contacts. 
Exceeding this rating may cause the relay to fail and prevent a trouble 
condition from being indicated. 