Technical data
Series SPB Audio Boosters Manual, Revision A 
5-1
5 Operation 
5.1 Introduction 
This chapter  describes  the  operating  characteristics  of  the  Series  SPB  Audio  Booster Panel. 
Included is information about the following panel features: 
Supervision 
Audio Notification Appliance Output Circuit Supervision 
Amplifier Supervision 
Actions that Initiate Alarms   
5.2 Supervision 
A TROUBLE LED indicates that the supervisory functions have detected a malfunction in the 
panel. When a trouble condition is detected, the panel may not be able to receive and/or broadcast 
messages from the host voice evacuation panel. 
If a trouble condition is detected by any of the supervisory functions, the internal sounder of the 
SP40S voice evacuation panel operates, the audio booster Form “C” TROUBLE relay (normally 
energized) changes state, and the yellow TROUBLE LED turns “ON.” The Trouble Status Relay 
may be used to provide an external audible or visual alert to indicate that the audio booster is in a 
trouble condition. At the same time, one of the yellow trouble location LEDs identifies the 
location of the trouble condition. If a trouble condition is indicated, follow the procedures in 
Chapter 8 "Troubleshooting.” 
 WARNING:  Do not leave the panel in a trouble condition, as it 
may  not  play  warning  messages  from  the  voice  evacuation  panel, 
which could result in serious injury or death to you and/or others. If 
the panel indicates a trouble condition: (1)  provide  UL required 
alternative  signaling  and  (2)  have  qualified  service  persons 
immediately replace unit(s) that have malfunctioned. 
    WARNING:    Messages  requested  before  and  during  a  trouble 
condition may not be heard, which could result in serious injury or 
death to you and/or others.  If messages requested before and during 
a trouble condition are still necessary, they should be repeated when 
the panel is returned to normal. 