Specifications
37
Chapter 5 Troubleshooting
5.1 System Reset Button
The system reset button is located above the RS485 COM1 Port. The location is shown in Figure 16. It is
used to reset the network configuration.
STANDBY / RUN
USB CONFIG
D27
D25
D17
RS485
COM1
TB5
RS485 COM1 ACTIVE
D24
RS485 COM2 ACTIVE
TROUBLE
D29
SPLITTER MISMATCH
D28
RS485 COMM LOSS
D26
USB Port
POWER
SYSTEM
RESET
System Reset
Button
Figure 16
Reset Button Location
5.1.1 Resetting the Network Configuration (Not SP4 Telzone
Programmer Programmed)
Resetting the network configuration is done when it appears that the paging system is corrupt or an
SP4-APS splitter has been added, removed or replaced. Should one of these conditions occur, and the
SP4-TZC has not been programmed using the SP4 Telzone Programmer software, perform this
procedure. If you have made changes, use Appendix A at the end of this manual to update the new
zone code location for each zone and zone group.
The procedure is as follows:
Remove the enclosure cover for the SP4-TZC.
Make sure 24VDC is ON to the SP4-TZC and all SP4-APS splitters.
Press and hold the reset button for approximately 5 seconds until the all LED indicators
except the POWER LED indicator turn OFF.
Release the button. The SP4-TZC will begin finding and mapping the SP4-APS splitters. The
“RS485 COM1 ACTIVE” LED indicator should be BLINKING. The “STANDBY/RUN”
LED will BLINK for a maximum of 1 minute before becoming solid ON.
Install the enclosure cover.
STEP 1
STEP 2
STEP 3
STEP 4
STEP 5