Enter the number of SP4-APS splitters used. (The maximum number of splitters is 17.)
NOTE: When the splitters are set to CLASS “A” the maximum number of Individual Zones is two per
splitter with a maximum of 34 per system. When the splitters are set to CLASS “B” the maximum
number of Individual Zones is four per splitter with a maximum number of 68 per system.
Remember, all SP4-APS splitter “Audio Class of wiring” settings must be the same.
Click the Next command button. The Background Music setup screen will appear:
Notice that 12 of the boxes are white. This represents active zones. This would be correct when the
“Audio Class of wiring” was set to CLASS “B” and the “Number of Splitters” was set to 3.
NOTE: When the Clear All command button is selected, all check marks are removed from the
zone boxes. When the Set All command button is selected, all zone boxes will contain a
check mark.
Edit the Background Music setup to play on the desired Individual Zones. The check mark
indicates that the Background Music will play on the indicated zone.
If Logical Zone Groups were not programmed, go to STEP 13.
Click the Finish command button. The main screen will appear.
STEP 7
STEP 8
STEP 9
STEP 10