Specifications

19
2.7.2 Adjustments on the SP4-TZC Zone Controller
The SP4-TZC has two adjustments described in Table 3. Refer to Figure 13 for locations of these volume
adjustments.
Table 3
SP4-TZC Adjustments
Adjustment Results
BGM Volume Adjust (R17) Clockwise for Volume Increase
Page Volume Adjust (R7) Clockwise for Volume Increase
PAGE
VOLUME
JP1
R7
AUDIO
OUT
TB3
BGM
INPUT
TB2
TIP
RING
TB1
R17
BGM VOLUME
JP1 SETTINGS
1-2 - ALERT PAGE TONE
2-3 - NO ALERT PAGE TONE
BGM Volume
Adjust
Page Volume
Adjust
PHONE IN
1
2 3
Figure 13
SP4-TZC Adjustment Locations
2.7.3 Testing the SAFEPATH
®
4 Multi-Function Facility
Communications System Paging Function
In the “out of the box” configuration, the paging function will only allow Individual Zones and Fixed Zone
Groups to operate. Background Music will be broadcast on all Individual Zones. In order to program
Logical Zone Groups and edit the Individual Zones for Background Music the SP4 Telzone Programmer
software must be used. The installation and use of the SP4 Telzone Programmer software is described in
Chapter 3.
Calculate the number of Individual Zones available. The number of Individual CLASS “B
Zones available equals the number of SP4-APS splitters times 4. The number of Individual
CLASS “A” Zones equals the number of SP4-APS splitters times 2.
(CLASS “A” = 2) or (CLASS “B” = 4)
x (# of SP4-APS splitters) = # of Individual Zones Available
Examples:
If I had 12 SP4-APS splitters, in order to calculate the number of CLASS “B” zones I would multiply the
number of splitters by 4. The result would be 48 Individual Zones available.
In order to calculate the number of CLASS “A” zones, I would multiply the number of splitters by 2. The
result would be 24 Individual Zones available.
STEP 1