Specifications
18
PAGE
VOLUME
JP1
R7
AUDIO
OUT
TB3
POWER
TB6
BGM
INPUT
TB2
R17
BGM VOLUME
JP1 SETTINGS
1-2 - ALERT PAGE TONE
2-3 - NO ALERT PAGE TONE
1 2 3
24VDC
Power Supply
Figure 11
24VDC Connection to the SP4-TZC
Apply power to the 24VDC Power Supply. The “POWER” LED indicator will turn ON. The
“RS485 COM1 ACTIVE” LED indicator should be BLINKING. The “STANDBY/RUN”
LED will BLINK for a maximum of 1 minute before becoming solid ON. See Figure 12 for
LED indicator locations.
NOTE: If an SP4-APS splitter is not energized during this process, the SP4-TZC will not “see” it and will
go to the next splitter. This will affect the order of the zone codes.
NOTE: If the “TROUBLE” LED indicator is ON, and the “SPLITTER MISMATCH” LED indicator is
ON, one or more of the CLASS switches on the SP4-APS splitters is in the wrong position. See
Figure 12 for LED indicator locations. Check the CLASS Switch on each splitter and make sure
all are in CLASS “A” or CLASS “B” as desired.
STANDBY / RUN
USB CONFIG
D27
D25
D17
RS485
COM1
TB5
POWER
TB6
RS485 COM1 ACTIVE
D24
RS485 COM2 ACTIVE
TROUBLE
D29
SPLITTER MISMATCH
D28
RS485 COMM LOSS
D26
24 VDC
Input
USB Port
Power On LED
Indicator (Green)
POWER
SYSTEM
RESET
RS485 COM1
ACTIVE LED
(GREEN)
TROUBLE LED
(ORANGE)
SPLITTER MISMATCH
LED (ORANGE)
STANDBY/RUN
LED (GREEN)
Figure 12
SP4-TZC LED Indicators
STEP 2