Specifications

Description:
Remote Microphone for use with the SAFEPATH
®
4 Facility
Communications System - SP40S-S, SP40S-D, SP40/2 or
SP4-RMX
Applications:
Provides for an additional microphone in a remote
location
• Can be mounted up to 2,000 feet away from the
SP40S, SP40S-D or SP40/2
Features:
Model
Order
Code
Description
SPRM 8996
Remote Microphone for use with SP40S,
SP40S-D SP40/2, SPB-320, SPB-160,
SPB-80/4 or SP4-RMX, red plate
SPRM-GP 9927
General Paging Microphone for use with
the SPB-320, SPB-160, or SPB-80/4,
black plate
Ordering Information:
Approvals: UL Standard 864, 9th edition and California
State Fire Marshal (CSFM)
Supervised hand held push to talk microphone
Key required to enable remote microphone use
Individual front panel LED indication for; System
Normal, System Trouble and Alarm
When used with the SP40S, SP40S-D or SP40/2, the
priority level is 2, the SP40S, SP40S-D or SP40/2 on
board microphone is always priority 1
Remote microphone usage disengages background
music and general paging
Voice frequency response: 275 Hz - 6.5 kHz
Requires 24VDC, supplied by the SP40S, Audio
Boosters, or SP4-RMX
Input current: Standby: 23mA
Alarm: 30mA
Audio output level: 1.05V RMS
6 wire connection to the SP40S, SP40S-D, SP40/2 or
SP4-RMX
Mounting plate is red and measures, 8 3/4” x 5 ¼”,
ts into a 4 gang back box
All output circuitry is Power Limited
SAFEPATH
®
4
RemoteMicrophone
11
Applications:
Features:
Model
Order
Code
Description
SP-SVC 9926
Supervised Volume Control for use
with the SAFEPATH®4 system
Ordering Information:
SAFEPATH
®
4
Supervised Volume Control
SP-SVC
Supervised Volume Control
Supervised volume control for use with UL
Listed Life Safety Applications
Can handle up to 35 watts of 70.7 volt audio
power input
Adjustment settings: 0 – 10, in 3dB increments
Operates in Class B or Class A wiring (for Class
A, the SP4-APS is required)
•· Requires a double gang, 3½” deep back box
or 4” square and 1-1/2” deep box with a 1-1/2”
extension ring
Stainless steel mounting plate with a black knob
UL Standard 864 and California State Fire
Marshal (CSFM) listed for use with the SP40S,
SP40S-D, SP40/2 or SPB Audio Boosters
OSHA 1910.165 and ADA compliant
Maximum RMS current 10.0mA
Allows manual volume setting for telephone
paging and background music for a specic
speaker or speaker zone
The selected adjustment will not affect the
volume setting of emergency prerecorded
messages or live microphone usage
10