Instruction manual
3-16
Section 3-6 - System Checkout
Refer to NFPA 72 (1999 Edition) for guidelines on testing notification systems.
System Control Settings
Figure 3-15 on Page 3-15 shows the location of the controls used to configure the SP40/2 Table
3-2, Page 3-16, explains the functions of the different jumpers, switches, and variable resistors.
The following procedure is a basic setup for the panel:
D14 STROBE ALARM LED (Red)
D13 TROUBLE LED (Yellow)
D11 POWER LED
(Green)
SW3 Digital Voice
Control DIP Switch
R128 Background Music
Volume Control
R89 Telephone Page
Vol ume Control
J4 Audio Output
Select
R193 Digital Voice
Vol ume Control
W2 Strobe Synchronization
Defeat
W1 DV Record
W3 Internal Tone
Select
W5 Contact Closure
Supervision
W4 Audio Short
Disable
D34 Record LED
DV Record
Microphone
_
_
+
_
+
+
TB6
_
_
+
_
+
+
TB4
TB3
_
_
+
_
+
+
TB2
_
_
+
_
+
+
TB5
1
2 3
4
ON
MIC1
U8
DV
D34
RECORD
W1
W2
D11
AC
GRN
RED
YEL
TBL
STB
STB
SHORT
AUX
STB
OPEN
GF
IN
AUDIO
SHORT
AUDIO
OPEN
AMP
MIC
DV
AUX
AC
BAT
100V
70V
25V
1V
25V
70V
100V
STB OUT
RET
STB IN
NO
NC
COM
A
L
M
T
R
B
NO
NC
COM
IN3
IN2
IN1
NR
TEL
BGM
AUDIO OUT
CC/NAC
AUX IN
TONE
BGM
TEL
NAC
CC
W5
W4
W3
E1
1
2 3
4
ON
1
2
3
R
Grounding Terminal
SW1
SW2 DV/Strobe Select
Sync/nonSync Select
SW1 Trouble Acknowledge
Switch
SW3
SW2
F2
AC
N
L
TB7
_
_
+
_
+
+
TB1
24V
BAT
IN
W8
W7
W7 Non Alarm
Disable
W8 Future Use
R126 Tone Control Bass
R129 Tone Control Treble
F1
J3
W6
W6 Ground Fault Disable
J3 Microphone Jack
Figure 3-15
Jumper/Switch/Variable Resistor Locations
1. Ensure that the AC and Battery Power are not connected.
2. Plug in the Microphone.
3. Select the proper audio output (25V or 70V) by using the two jumpers on J4 Audio Output
Select.
4. Connect the speaker circuit to terminal block TB6 AUDIO OUT. Verify that the speaker
circuit has a UL Listed 10K Ohm, ½ W EOLR.
5. If applicable, connect the strobe circuit to TB2 STB OUT. Verify that the strobe circuit has
a UL Listed 10K Ohm, ½ W EOLR.
6. If Strobe synchronization is to be defeated, remove Jumper W2 Strobe Synchronization
Defeat.