Instruction manual

3-14
Section 1
Power Input Connections
_
_
+
_
+
+
TB1
24V
BAT
IN
Figure 3-13
Input Power and Battery Connection Locations
Proceed to Step 2 in Section 3-3 – General Installation Instructions (Page 3-4)
.
Section 3-5 - Mounting
Location
The SP40/2 panel shall be mounted in a location within the environmental limits specified in the
latest UL Standard 864 for indoor control panels. The SP40/2 panel shall not be located in a
hazardous area.
CAUTION: In order to comply with the latest NFPA and UL requirements for interconnection
of fire alarm control equipment, the SP40/2 must be located in the same room, and within 20 feet
of, a listed compatible fire alarm control panel. Wiring shall be enclosed in conduit and properly
connected to such control panel.
1. See Figure 3-14 on Page 3-14 for SP40/2 panel mounting hole layout.
2. Mark and drill mounting holes for appropriate screws and anchors to ensure secure
mounting to the type of surface at the selected location.
3. Prevent dust and dirt contamination of the SP40/2 panel during installation. This
contamination can interfere with the operation and reduce the life of the equipment.
4. Open the door and remove the dead front panel, and mount the SP40/2 panel at the
selected location. Use care to avoid damage to the module during installation. Do not
apply excessive pressure to the PC board or its components, including field wiring terminals
and connectors.
5. Proceed to step 4 in Section 3-3 – General Installation Instructions (Page 3-4).