Instruction manual

3-13
NO
NC
COM
TB3
A
L
M
Figure 3-11
Alarm Relay Contacts
Trouble Output Contact Wiring
The locations of the Trouble Status Output Connections are shown in Figure 3-1 Section 1
(Page 3-2). A magnified view of this area on the Mother Board is shown in Figure 3-7 on
Page 3-7.
Wire gauge selection of the system Trouble Status output contact wiring should involve
consideration of all factors including, wire length, maximum current capacity, and
maximum voltage drop allowable.
The system Trouble Status output contact is Form C, rated for 2.0 amps at 24VDC,
resistive load.
For a detail of the system Trouble Status output contact terminal connections (shown in
the trouble position), see Figure 3-12 below.
An external 24VDC or the internal 24VDC connection (TB1) can be used to power
Trouble indicating appliances. See Figure 3-1, Section 1 (Page 3-2) for location of TB1.
NO
NC
COM
TB3
T
R
B
Figure 3-12
Trouble Status Relay Contacts
POWER CONNECTION REQUIREMENTS
The SP40/2 contains a 24VDC Power Supply and a Battery Charger for the battery backup.
Connections for the input power and batteries are shown in Figure 3-1, Section 1 (Page 3-2). A
magnified view of this area on the Mother Board is shown in Figure 3-13, below. TB1 is for
battery connection. TB1 has a 24VDC, 0.5A, power limited, auxiliary power source. Calculate
proper backup battery requirements using Section 3-8 – Battery Care and Backup Battery
Calculations.(Page 3-19). Section 3-9 on Page 3-21 is the AC and battery installation
procedures.