Instruction manual
3-13
NO
NC
COM
TB3
A
L
M
Figure 3-11
Alarm Relay Contacts
Trouble Output Contact Wiring
• The locations of the Trouble Status Output Connections are shown in Figure 3-1 Section 1
(Page 3-2). A magnified view of this area on the Mother Board is shown in Figure 3-7 on
Page 3-7.
• Wire gauge selection of the system Trouble Status output contact wiring should involve
consideration of all factors including, wire length, maximum current capacity, and
maximum voltage drop allowable.
• The system Trouble Status output contact is Form C, rated for 2.0 amps at 24VDC,
resistive load.
• For a detail of the system Trouble Status output contact terminal connections (shown in
the trouble position), see Figure 3-12 below.
• An external 24VDC or the internal 24VDC connection (TB1) can be used to power
Trouble indicating appliances. See Figure 3-1, Section 1 (Page 3-2) for location of TB1.
NO
NC
COM
TB3
T
R
B
Figure 3-12
Trouble Status Relay Contacts
POWER CONNECTION REQUIREMENTS
The SP40/2 contains a 24VDC Power Supply and a Battery Charger for the battery backup.
Connections for the input power and batteries are shown in Figure 3-1, Section 1 (Page 3-2). A
magnified view of this area on the Mother Board is shown in Figure 3-13, below. TB1 is for
battery connection. TB1 has a 24VDC, 0.5A, power limited, auxiliary power source. Calculate
proper backup battery requirements using Section 3-8 – Battery Care and Backup Battery
Calculations.(Page 3-19). Section 3-9 on Page 3-21 is the AC and battery installation
procedures.