Instruction manual

2-1
Chapter 2 - Overview and Features
Section 2-1- Description
General
The SP40/2 panel is a stand alone, single channel, 40 watt, supervised voice evacuation/emergency
message system with additional features of a Telephone Page Input, Night Ring Input and
Background Music Input. Figure 2-1 illustrates the basic capabilities.
The control panel that activates the SP40/2 panel must provide a Notification Appliance Circuit with a
voltage ranging from 9 to 31VDC.
The SP40/2 panel does
not
sense an emergency condition or hazards such as fire; it is only a part of
a system that does sense such conditions. The SP40/2 panel, when activated, provides a pre-
recorded voice message(s) to speaker notification appliances. When used as part of a protective
signaling system, the SP40/2 panel must be properly connected to a compatible control panel that
has been approved by a nationally recognized testing laboratory ("LISTED") and to LISTED
compatible notification appliances for proper operation.
THE SP40/2 PANEL MUST BE PROPERLY INSTALLED, PROGRAMMED, AND CONNECTED TO
A COMPATIBLE FIRE ALARM CONTROL PANEL TO FUNCTION IN A VOICE EVACUATION
SYSTEM.
WHEELOCK EXPRESSLY DISCLAIMS ALL LIABILITY FOR THE CONTENT, CLARITY AND
LANGUAGES OF, AND OUTPUT CHANNEL AND PRIORITY LEVEL ASSIGNED TO, ANY AND
ALL MESSAGES. IT IS ESSENTIAL THAT YOU HAVE MESSAGE CONTENT AND LANGUAGE,
SEQUENCE, OUTPUT CHANNEL AND PRIORITY ASSIGNMENTS REVIEWED AND APPROVED
BY QUALIFIED LEGAL AND SAFETY ADVISORS, QUALIFIED REPRESENTATIVE(S) OF
OWNER(S) AND USER(S), AND AUTHORITIES HAVING JURISDICTION.
Standard Features
One strobe NAC output section.
24VDC @ 2 Amps Maximum.
Requires separate NAC Circuit (9 to 31VDC) input or can be programmed to operate when
Digital Voice messages are played.
Return allows pass through for Wheelock synchronized strobes, remote SP40/2 panels,
additional strobe appliances or EOLR.
Synchronized output when using Wheelock’s Synchronized strobe products.
Supervised with 10K Ohm EOLR.
Trouble LEDs for Open and Short conditions.
40 Watt Audio Amplifier section.
Selection of 25Vor 70V speaker output.
Supervised with 10K Ohm EOLR.
Trouble LEDs for Open and Short Conditions