Instruction manual

10-1
Chapter 10 - MEA and Warranty
Recommendations - That the above units be accepted on condition that all uses, configurations, arrangements and
functions, locations and installations comply with the New York City Building Code, specifically Subchapter 17 and
with the Referenced Standard RS 17-3 through 17-3C including the NFPA as appropriate, the UL Listing, the
manufacturer’s instructions, the Fire Department Rules and the Electrical Code of the City of New York, and on
further condition that:
(a) The use, installation and application of the SAFEPATH
®
System shall be restricted exclusively to connection
with an BSA/MEA approved compatible Class E, Class J or Class C Fire Command Station.
(b) The Fire Command Station shall have the capability of overriding any function of the SAFEPATH
®
System.
(c) Prior to the installation of any SAFEPATH
®
System, a specific approval for a specific installation must be
obtained from the Fire Department.
(d) A priority voice message matrix must be submitted to the Fir Department for approval before the installation is
performed and shall include the following information:
1. The duration of each message.
2. The content of each message.
3. The duration of the audible and visual alarm signals prior to the initiation of the subsequent prerecorded
message transmission.
4. The interval between the cessation of the audible and visual alarm signals and the generation of
prerecorded message.
(e) The SAFEPATH
®
Panel must be located in the room as, and within 20 feet of a BSA/MEA approved Fire
Command Station. The wiring between the SAFEPATH
®
Panel Control Unit and the Fire Command Station
must be enclosed in conduit.
(f) Power supply wiring to the SAFEPATH
®
Panel Control Unit shall be installed in the same conduit containing the
input and output wiring.
(g) When used with central office communicator or transmitter, the installation and operation of the equipment and
devices listed herein shall comply with Fire Department Rule #3 - RCNY 17-01, NFPA 71, and shall have the
capability of transmitting separate and distinct signals to indicate manual pull station alarm, automatic
smoke/heat detection alarm, sprinkler waterflow alarm, supervisory signal indications and trouble indications.
(h) The connection of security/burglar devices and equipment to that submitted for acceptance for fire alarm usage
under this MEA application is prohibited within New York City and such equipment and devices shall be so
permanently labeled.
All shipments and deliveries of such equipment shall be provided with a metal tag suitably placed, certifying that the
equipment shipped or delivered is equivalent to that tested and accepted for use, as provided for in Section 27-131 of
the Building Code.