Instruction manual

3-10
IN8
IN7
IN6
IN5
IN4
IN3
IN2
IN1
TB 2
RV1
TB 3
RV8
RV5
D11
RV7
RV6
RV3
RV4
RV2
Digital Voice Module
MDX-2
Figure 3-11
Dry Contact Input Connections
ALARM STATUS OUTPUT CONTACT WIRING
TB1
TRB AUD
TRB COM
TRB NO
TRB NC
ALARM COM
ALARM NO
ALARM NC
+
-
Motherboard (SCMB)
Figure 3-12
Alarm and Trouble Status Output Connections
The location of the Alarm Status output connections are shown in Figure 3-10 Section 2 on Page 3-
10. A magnified view of this area on the Mother Board is shown in Figure 3-12 on Page 3-11.
Wire gauge selection of the Alarm Status output contact wiring should involve consideration
of all factors including, wire loop length, maximum current capacity, and maximum voltage
drop allowable.
The Alarm Status output contact is Form C, rated for 0.5 amps at 24VDC, resistive load.
For terminal connection details of the Alarm Status output contact (shown and marked in
the non-alarm mode) see Figure 3-13.