R EV: P 8 3 4 12 R E V ( ) SN : U 17 D1 D2 AMBER GREEN C 50 U 16 SAFEPATH P83167 REV B F1 R71C 47 R72 C 49 R73 R V 10 C 46 S 15 U 15 T1 + K2 K1 R70 SAFEPATH R69 Q2 RV9 D 12 C 4 8 C 45 R66 U 14 Q1 R67 S 14 SW1 SW2 U 13 D 13 R 6 8 RV8 C 43 R65 C 44 K3 SW3 U1 ® TB1 TRB AUD - TRB COM TRB NO TRB NC ALARM COM ALARM NO ALARM NC + F2 DV POWER - U 12 S 12 D 10 + R62 J6 TB 3 Installation, Testing, Operation, and Maintenance Manual DV STATUS +LINE OUT + -LINE IN
Intentionally Blank
Typographical Notation Conventions Thank you for using our products. Use this product according to this instruction manual. Please keep this instruction manual for future reference.
Intentionally Blank iv
TABLE OF CONTENTS Typographical Notation Conventions…………………………………………………………… iii Table of Contents…………………………………………………………………………………. v Table of Figures…………………………………………………………………………………… vii Table of Tables……………………………………………………………………………………. ix Chapter 1 – Safety Precautions…………………………………………………………………. 1-1 Section 1-1 – Read This Manual………………………………………………………….
Section 5-2 – To Make Live Announcements………………………………………….. Section 5-3 – To Sound Evacuation Tone……………………………………………… Section 5-4 – To Reset Visual Appliances……………………………………………… Section 5-5 – To Acknowledge a Trouble Condition………………………………….. 5-1 5-1 5-2 5-2 Chapter 6 – Periodic Testing and Maintenance………………………………………………. 6-1 Section 6-1 – Periodic Testing…………………………………………………………… 6-1 Section 6-2 – Qualified Personnel..……………………………………………………… 6-1 Section 6-3 – Miscellaneous Hardware Testing ……………………………………….
List of Figures Figure 2-1 Basic Capabilities of the Single Circuit SAFEPATH® Panel………………………... 2-2 Figure 2-2 Module Layout of a Typical Single Circuit SAFEPATH® Panel………………… 2-5 Figure 3-1 Location of Plug-in Modules and Wire Connections……………………………… 3-2 Figure 3-2 Strobe and Audio Output Connections…………………………………………….
Figure 9-6 Supervised Audio System Amplifier/Signal Circuit Module, 80 Watts (SAA-80S/SE)………………………………………………………………………… 9-12 Figure 9-7 Supervised Audio Line Level Module (SALL-15S)………………………………. 9-14 Figure 9-8 Notification Appliance Circuit Interface Module (NACIM)………………………… 9-15 Figure 9-9 4-Zone Splitter Module (SC-SPL)…………………………………………………. 9-16 Figure 9-10 Auxiliary Input Module (AIM-3)……………………………………………………. 9-18 Figure 9-11 Remote Microphone Station (RMS-2)…………………………………………….
LIST OF TABLES Table 3-1 SCMB DIP Switch Setting Description……………………………………………… 3-17 Table 3-2 DIP Switch Settings for Available Tone Sounds…………………………………… 3-17 Table 3-3 Standby Current for Single Circuit SAFEPATH® Panel………………………….. 3-20 Table 3-4 Standby and Alarm Current for Single Circuit SAFEPATH® Modules………….. 3-21 Table 3-5 Standby Current for Single Circuit SAFEPATH® Amplifier Modules……………. 3-21 Table 3-6 Calculations for Amplifier Alarm Current………………………………..………….
Intentionally Blank x
Chapter 1 - Safety Precautions Section 1-1 - Read This Manual Personnel properly qualified in the application and use of life safety equipment ("qualified personnel") shall read this manual carefully before performing any actions to specify, apply, install, maintain and operationally test SAFEPATH® Panel products in accordance with the instructions in this manual. This manual shall be kept with the SAFEPATH® Panel for reference during the life of the system.
Notification equipment cannot last forever. Even though SAFEPATH® Panel is expected to last up to ten years, any of its parts or components could fail before then. Therefore testing of the entire protective signaling system, including the SAFEPATH® Panel, all notification equipment, as well as all messages and their output channel, and priority assignment, shall be conducted at least twice each year, or more often as required by local, state and federal codes, regulations and laws, by qualified personnel.
Section 1-5 - Audio Output Considerations WARNING: AUDIBLE SIGNALS MAY MASK MEDICAL EQUIPMENT MONITORING ALARMS. WHERE MEDICAL EQUIPMENT MONITORING ALARMS ARE IN USE, DO NOT USE AUDIBLE SIGNALS; PROVIDE VISUAL NOTIFICATION APPLIANCES IN HIGHLY VISIBLE LOCATIONS. CAUTION: The output of the audio system may not be heard in all cases.
Intentionally Blank 1-4
Chapter 2 - Overview and Features Section 2-1- Description General The Single Circuit SAFEPATH® Panel is a stand alone, single channel, supervised audio fire and emergency evacuation system. Figure 2-1 on Page 2-2 illustrates the basic capabilities of the Single Circuit SAFEPATH Panel. The control panel that activates the Single Circuit SAFEPATH Panel can range from simple push buttons to a sophisticated computer based control panel providing dry contact closures.
• • Optional remote microphone station • Digital Voice Module (MDX-2) • Alarm input activation wiring • Input voltage/low battery Built-in audible alert indicates any supervision loss • Auxiliary trouble output for trouble signal connection • Remote reporting via output contacts for system trouble or alarm activation. • An internal 6-amp power supply/ 40Ah battery charger. Optional Features • Remote Microphone Station (RMS-2) for live, emergency announcements.
Section 2-4 - Module Configurations The Single Circuit SAFEPATH® Panel is equipped with a combination of the following modules: There are ten modules in the Single Circuit SAFEPATH Panel product line.
Section 2-7 - Operation Modes The SAFEPATH® Panel has two operation modes: 1. Standby 2. Alarm Standby Mode Standby is the normal mode. The SAFEPATH® Panel supervises the connections and internal components to maintain proper operation. All strobes and speaker appliances are off. Alarm Mode Alarm mode occurs when an emergency signal is initiated manually, or by the FACP or control equipment.
2-5 Figure 2-2. Module Layout of a Typical Single Circuit SAFEPATH® Panel 4 Way Splitter (SC-SPL) ZONE 4 Zone active LED's indicate the active zones. Power Supply/ Battery Charger (DCPS) Zone select LED's indicate the selected zones. Use all-call to select all zones. Use zone switches to select zones for live announcements.
Intentionally Blank 2-6
Chapter 3 - Installation and Setup Section 3-1 - Introduction The lives of people depend upon the safe and proper installation of the SAFEPATH® Panel. Please read, understand and carefully follow the specific installation instructions set forth below to avoid damage to the SAFEPATH® Panel and equipment connected to it. Only qualified personnel in accordance with the procedures in this manual should conduct installation. WARNING: SHUT OFF ALL POWER BEFORE STARTING THE INSTALLATION.
Amplifier Connector Digital Voice Module MDX-2 TRB AUD - TRB COM TRB NO TRB NC ALARM COM ALARM NO TB1 D2 P 8 3 4 12 R E V ( ) SN : C 50 R 71 C 4 7 R 72 T1 GREEN + K2 K1 TRB AUD - TRB COM TRB NO TRB NC ALARM COM ALARM NO R 70 U 14 U1 R V8 C 43 - R 65 U 12 D 10 R 62 J6 R 45 R 46 C 33 R 47 R 48 C 34 R 49 R 50 C 35 R 51 R 52 C 36 R 53 R 54 C 38 R 55 R 56 C 39 R 57 R 58 C 40 R 59 R 60 C 41 R 61 C 4 2 J5 DV STATUS -CH PLAY -LINE IN + U 11 X1 - RM RXD + R 41 R 38 C 3 2 R 43 U 10
5. Connect conduit fittings or bushings as needed through the knockouts provided on the top and bottom of the SAFEPATH® Panel. Field Wiring Connections 6. Install field wiring in conduit when required, following the most current National Electrical Code (NFPA-70) and local codes for the type of system being installed. Make all necessary connections at any additional wiring or junction boxes. 7.
Initial Checkout WARNING: TWO DIFFERENT SOURCES OF POWER MAY BE CONNECTED TO THE SAFEPATH® PANEL. DISCONNECT BOTH SOURCES OF POWER BEFORE SERVICING. FAILURE TO DO SO COULD RESULT IN PROPERTY DAMAGE, SERIOUS INJURY, OR DEATH TO YOU AND/OR OTHERS. CAUTION: Connect the AC power source before connecting the battery backup power. Disconnect the battery backup power before disconnecting the AC power source. 1. Conduct the Initial Checkout procedures as described in Section 3-6 System Checkout. Final Checkout 2.
CAUTION: The National Electric Code limits the maximum number of conductors that can be installed in conduit and wiring boxes depending on the size of the conduit, the volume of the boxes, and the gauge of the wire used. Make sure that wiring used for SAFEPATH® Panel installation complies with the latest NEC, NFPA, Local, State, County or Province requirements. Field Wiring Connections All SAFEPATH® Panel wiring terminals are designed to accept #12 AWG through #22 AWG wiring (one wire per terminal).
STROBE + _ UL LISTED 10K Ohm 1W EOLR AUDIO + _ UL LISTED 10K Ohm 1W EOLR Figure 3-4 Wiring Diagram for Combination Audio/Visual Notification Appliances in Central Amplifier Applications CAUTION: Do not loop wire under terminals. Break wire run to provide supervision of connection.
• • • The central amplified output is either a selectable 25, 70.7 or a 100 volt audio output, rated for 40, or 80 watts maximum, depending upon the amplifier and its configuration. The output meets Class B supervision requirements for notification appliance circuits. Each output circuit shall have a UL LISTED, 10K Ohm, 1W EOLR installed across the last audio notification appliance. If the output is unused, it shall have a UL LISTED, 10K Ohm, 1W EOLR across the output terminals.
Wiring Diagrams for Audio and SPK AMP Portions of Self-Amplified Audio/Visual Notification Appliances SPKR AMP AUDIO + _ UL LISTED 10K Ohm 1W EOLR + _ UL LISTED 10K Ohm 1W EOLR Figure 3-8 Wiring Diagram for Audio Notification Appliances in Amplified Speaker Applications CAUTION: Do not loop wire under terminals.
INTERNAL WIRING CONNECTIONS Amplifier Connector Digital Voice Module MDX-2 TRB AUD - TRB COM TRB NO TRB NC ALARM COM ALARM NO TB1 D2 P 8 3 4 12 R E V ( ) SN : C 50 R 71 C 4 7 R 72 T1 GREEN + K2 K1 TRB AUD - TRB COM TRB NO TRB NC ALARM COM ALARM NO R 70 SW3 U1 U 14 R V8 C 43 R 65 DV POWER - + U 12 DV STATUS + CH PLAY +LINE OUT + -LINE IN S 12 D 10 R 62 J6 R 45 R 46 C 33 R 47 R 48 C 34 R 49 R 50 C 35 R 51 R 52 C 36 R 53 R 54 C 38 R 55 R 56 C 39 R 57 R 58 C 40 R 59 R 60 C 41 R 61
Digital Voice Module MDX-2 RV8 IN8 IN7 RV6 D11 RV7 TB 3 IN6 IN5 RV5 IN4 RV4 IN3 RV3 IN2 RV2 IN1 RV1 TB 2 Figure 3-11 Dry Contact Input Connections ALARM STATUS OUTPUT CONTACT WIRING Motherboard (SCMB) + TRB AUD - TRB COM TRB NO TRB NC ALARM COM ALARM NO TB1 ALARM NC Figure 3-12 Alarm and Trouble Status Output Connections The location of the Alarm Status output connections are shown in Figure 3-10 Section 2 on Page 310.
TB1 6 ALARM COM 7 ALARM NO 8 ALARM NC Figure 3-13 Alarm Relay Contacts System Trouble Status Output Contact Wiring The location of the Trouble Status output connections are shown in Figure 3-10 Section 2 on Page 310. A magnified view of this area on the Mother Board is shown in Figure 3-12 on Page 3-11.
TB1 TRBL AUDIO 24VDC GRND + 1 _ 2 Figure 3-15 Trouble Audible Connection Ground Fault Detection Wiring On the Mother Board, connect Earth Ground Connection (E1) as shown on Figure 3-1 on Page 3-2 to the Chassis Ground (Figure 3-17 on Page 3-15). Make sure that chassis ground is at earth ground or to the common ground of the FACP. Conduct the sensitivity adjustment as described in Section 3-7 Ground Fault Detection Sensitivity Adjustment.
Digital Voice Module MDX-2 R EV : P 8 3 4 12 R E V ( ) SN : U 17 C 50 U 16 R71C 47 R72 C 49 R73 R V 10 C 46 S 15 U 15 R70 R69 Q2 RV9 D 12 C 4 8 C 45 R66 U 14 Q1 R67 S 14 U 13 D 13 R 6 8 RV8 C 43 R65 C 44 U 12 S 12 D 10 R62 J6 R45 R46 C 33 R47 R48 C 34 R49 R50 C 35 R51 R52 C 36 R53 R54 C 38 R55 R56 C 39 R57 R58 C 40 R59 R60 C 41 R61 C 42 J5 U 11 D1 C 37 SAFEPATH P83167 REV B AMBER R41 R38 C 32 R43 U 10 T1 D2 F1 GREEN K2 K1 R40 C 31 C 28 C 29 C 30 R39 R42 R44 RV6 R 6
Procedure 1. See Figure 3-17 on Page 3-15 for SAFEPATH® Panel mounting hole layout. 2. Remove Amplifier Module from the enclosure. 3. Mark and drill mounting holes for appropriate screws and anchors to ensure secure mounting to the type of surface at the selected location. 4. Prevent dust and dirt contamination of the SAFEPATH® Panel during installation. This contamination can interfere with the operation and reduce the expected life of the equipment. 5.
Section 3-6 System Checkout Refer to NFPA 72 (1999 Edition) for guidelines on testing notification systems. CAUTION: If a malfunction, or system trouble occurs during testing, STOP TESTING. Correct the problem before you resume testing. Insure that speaker and strobe NAC Circuits are not connected to the SAFEPATH® Panel, and that 10K Ohm ¼W EOLR test resistors are connected in their place on the Mother Board. 1.
Final Checkout CAUTION: If a malfunction, or system trouble occurs during testing, STOP TESTING. Correct the problem before you resume testing. CAUTION: Connect the AC power source before connecting the battery backup power. Disconnect the battery backup power before disconnecting the AC power source. 1. Set Configuration Switches to desired settings for supervision tone. See Figure 3-18 on Page 3-17 for switch location on the Motherboard (SCMB). See Tables 3-2 and 3-3 for switch descriptions.
Table 3-1 SCMB DIP Switch Setting Description DCDC DIP Switch SETTING/DESCRIPTION SW4 Position 1 (GND FLT ENB) GROUND FAULT ENABLE enables the ground fault detection circuit on the Motherboard SW4 Position 2, 3, 4 (1, 2, 3) MULTITONE SELECT selects 1 of 8 tones used for the secondary evacuation signal. Use chart below to select the tone. SW4Position 1, (LAMP TEST) LAMP TEST when enabled lights all the LED indicators on the Motherboard, and the Amplifier Module.
LED D13 (AUDIO) “OFF” LED D10 (PWR) “OFF” LED D3 (AMP) “OFF” 4. Play each messages by momentarily shorting IN1 through IN8 in turn on Digital Voice Module. See Figure 3-11 on Page 3-11. Relay on SCMB clicks at 1 click per second during the playing of each message. Message will broadcast on all appliance circuits. If Strobe NAC circuits are in use, Strobes will also flash. 5. Key Microphone in panel. Relay closure can be heard. Message will broadcast on all appliance circuits.
3. Rotate the shaft of the Ground Fault Detection Sensitivity potentiometer (R53) fully counterclockwise. (See Figure 9-2 on Page 9-5 for location) The potentiometer is a 12-turn device, there will be need to rotate the shaft repeatedly. The potentiometer produces a clicking sound when rotated beyond its end point. 4. On the Mother Board (SCMB), place a resistor with the desired set-point value (40K Ohm to 500K Ohm, +/- 5% Tolerance) between the +24VDC terminal on TB4 and the earth ground terminal.
Calculating Backup Battery Requirements A battery calculation worksheet is available at the back of this manual for assisting in calculating battery backup. It is necessary to calculate the current draw for battery backup requirements, The current requirements depend on the system configuration and the optional modules installed. Battery Backup current has two separate calculations that are added together. They are Standby Current and Alarm Current.
Table 3-4 Standby and Alarm Current for Single Circuit SAFEPATH® Modules SAFEPATH Module SCSP4 MDX-2 SPL AIM-3 RMS-2 NACIM 4 5 SAA-40S SAA-80S/SE SALL-15S7 7 Alarm Current 0.150 0.070 0.040 0.040 0.040 0.000 0.150 0.090 0.190 0.060 0.0605 0.007 Current draw with no amplifier and no Digital Voice Module installed. Current during RMS-2 page is 0.060 Amps. Current during telephone page is 0.100 Amps.
Table 3-6 Calculations for Amplifier Alarm Current 1 2 Amplifier Module Alarm Current Calculation SAA-40S1 [(Total wattage of connected speakers) X 55] + 0.4A SAA-80S/SE1 [(Total wattage of connected speakers) X 56] + 0.6A SALL-15S1, 2 (Sum of the “SPKR AMP” current) + 0.1A If Strobe NAC Circuit is used, add total strobe current on that circuit to the corresponding amplifier module calculation. A Strobe NAC Circuit cannot exceed 2 Amps of current.
3-23
Chapter 4 - OPERATION Section 4-1- Introduction This chapter describes the operating characteristics of the SAFEPATH® Panel.
WARNING: MESSAGES REQUESTED BEFORE AND DURING A TROUBLE CONDITION MAY NOT BE HEARD, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. IF MESSAGES REQUESTED BEFORE AND DURING A TROUBLE CONDITION ARE STILL NECESSARY, THEY SHOULD BE REPEATED WHEN THE SAFEPATH® PANEL IS RETURNED TO NORMAL. Visual Notification Appliance Output Circuit Supervision The visual notification appliance output circuit is supervised for open and short circuits when the output is de-energized.
Table 4-1 Alarm Conditions and Results PRIORITY OF EVENT 1. 2. 3. 4. 5. INITIATING ACTION Panel microphone push-to-talk button, is depressed. Automatic /Manual switch placed in manual position. Optional remote Mic key is on, and remote Mic push-to-talk button is depressed. Optional remote Mic key is on, and remote Mic auto/manual switch is in manual position. Contact closure inputs RESULT a. Panel microphone live voice broadcast enabled b. Strobes enabled (See Note 2) a. Selected tone broadcasts b.
Intentionally Blank 4-4
Chapter 5 - Operational Procedures Section 5-1 - Operator Instructions The SAFEPATH® Panel provides an operator console for manually activating the panel. The operator console includes a microphone, a green NORMAL LED, a yellow TROUBLE LED, a “RESET” momentary switch, a TROUBLE ACKNOWLEDGE momentary switch, and a MANUAL/AUTOMATIC switch.
2. Slide the AUTOMATIC/MANUAL switch down to the MANUAL position. The selected tone will play. Turn off the tone by returning the AUTOMATIC/MANUAL Switch to the UP position. See Figure 5-1 on Page 5-3 for switch location. See the Remote Microphone Station instruction sheet P83270 for additional information. Section 5-4 - To Reset Visual Appliances 1. All activation inputs must be cleared. 2. Depress the RESET momentary switch. See Figure 5-1 on Page 5-3 for switch location.
WhentheGREEN“NORMAL”LIGHT IsON,thesystem isfunctioning Properly. WhentheYELLOW “TROUBLELIGHT isON,thereisaFAULTinthe system whichMUSTBECORRECTED. STATUS TROUBLE NORMAL ! Warning: IFTHEYELLOW “TROUBLE”LIGHTISON, THISUNITMAYNOTBEABLETOPROVIDE EMERGENCYMESSAGEANNOUNCEMENT CAPABILITIESANDCOULDRESULTINPROPERTY DAMAGE.SERIOUSINJURYORDEATHTOYOU AND/OROTHERS.INTHEEVENTTHE “TROUBLE”LIGHTISON,YOUSHOULDCONTACT YOURSERVICEREPRESENTATIVEIMMEDIATELY. ACKNOWLEDGEMENT ToAcknowledgeaTroubleCondition: 1.
Intentionally Blank 5-4
Chapter 6 - Periodic Testing and Maintenance Section 6-1 – Periodic Testing Periodic testing of emergency notification equipment, including the SAFEPATH® Panel, all notification equipment and all messages, including their audibility and intelligibility, content and language, sequence, and priority assignment, must be conducted frequently, at least twice each year, or more often as required by local, state and federal codes, regulations and laws, by qualified personnel to ensure proper operation of all equip
Intentionally Blank 6-2
Chapter 7 – Troubleshooting Section 7-1 - Troubleshooting WARNING: SOME ELECTRONIC COMPONENTS STORE A HIGH VOLTAGE CHARGE, EVEN THOUGH POWER IS NOT CONNECTED, AND CAN CAUSE A DANGEROUS SHOCK IF TOUCHED. DO NOT TOUCH EXPOSED CIRCUITRY ON THE SAFEPATH® PANEL UNLESS THE CIRCUITRY HAS DISCHARGED FOR ONE HOUR AND A SAFE DISCHARGE PROCEDURE IS USED. WARNING: PROVIDE UL REQUIRED ALTERNATIVE SIGNALING MEANS DURING TROUBLE CONDITIONS AND SERVICING TO ASSURE ADEQUATE PROTECTION OF PEOPLE AND PROPERTY.
The internal trouble sounder and the external trouble audible will resound for subsequent trouble conditions. When there are no trouble conditions detected, the NORMAL LED will always be “ON” and the TROUBLE LED will always be “OFF”. When a trouble condition is detected, the NORMAL LED will always be “OFF” and the TROUBLE LED will always be “ON”. Figure 7-1 shows the location of all trouble location indicators within the panel.
Table 7-1 Module Trouble Procedure Cross Reference Mother Board (SCMB) NORMAL LED TROUBLE LED ON OFF OFF OFF Power Loss ON ON Faulty Mother Board B OFF ON Visual Notification Circuit Audio Output Wiring 24VDC Speaker Power SAA/SALL Module Remote Microphone Trouble Digital Voice Module Trouble C D E F G See Table 7-2 Module LED Trouble Description Troubleshooting Procedure Normal SAA/SALL RMS-2 MDX-2 STROBE AUDIO PWR AMP TROUBLE TROUBLE A Table 7-2 MDX-2 Trouble Procedure Cross Refere
Single Circuit Safepath Not Operating TROUBLE LED "ON" NO NORMAL LED "ON" NO Power Loss Procedure A YES Faulty Mother Board (SCMB) Procedure B YES TROUBLE LED "ON" NORMAL LED "OFF" SAA/SALL STROBE LED "ON" YES Refer to Procedure C NO SAA/SALL AUDIO LED "ON" YES Refer to Procedure D YES Refer to Procedure E NO SALL PWR LED "ON" NO To Sheet 2 of Figure 7-2 Figure 7-2, Sheet 1 of 2 Basic Troubleshooting Flowchart 7-4
From Sheet 1 of Figure 7-2 NO SAA/SALL AMP LED "ON" YES Refer to Procedure F YES Refer to Procedure G YES Refer to Procedure H NO RMS-2 TROUBLE LED "ON" NO MDX-2 NORMAL and TROUBLE LEDS "OFF" NO MDX-2 TROUBLE LEDS "ON" Refer to Figure 7-3 Figure 7-2, Sheet 2 of 2 Basic Troubleshooting Flowchart 7-5
From Sheet 2 of Figure 7-2 MDX-2 D6 LED "ON" MDX-2 D7 LED "ON" NO MDX-2 Inoperative Procedure I YES MDX-2 Inoperative Procedure J YES Message Memory EPROM error Procedure K YES Output Channel Error Procedure L YES MDX-2 D7 LED "Steady ON" NO MDX-2 D7 LED "2 Blink" NO MDX-2 D7 LED "4 Blink"L Figure 7-3 Digital Voice Module (MDX-2) Troubleshooting Flowchart 7-6
WARNING: BEFORE PERFORMING ANY OF THE FOLLOWING TROUBLESHOOTING PROCEDURES, THE PRELIMINARY TROUBLESHOOTING INFORMATION AT THE BEGINNING OF THIS “TROUBLESHOOTING” SECTION ON PAGE 7-1, MUST BE READ, UNDERSTOOD, AND FOLLOWED. Procedure A If the green NORMAL LED is “OFF”, the yellow TROUBLE LED is “OFF”, and no module LEDs are “ON”, then a power loss condition has occurred. A power loss condition may be caused by: 1. 2. 3. 4. Loss of AC input voltage and/or battery back-up voltage.
Perform the following: 1. 2. 3. 4. 5. Check EOLR and verify that it is a UL LISTED, 10K Ohm, 5% Tolerance, 1W Resistor. Check that the EOLR is properly in place. Verify that the Visual Notification Output field wiring is intact. Verify that all fuses on the SAA/SALL module are functioning. If trouble does not clear, remove strobe appliance circuit wiring from Motherboard and place a 10K Ohm 1/4W minimum resistor on strobe output (Figure 3-1 on Page 3-2).
Procedure F On the Single Circuit Mother Board (SCMB), the green NORMAL LED is “OFF”, the yellow TROUBLE LED is “ON”, and the AMP LED on the SAA/SALL module is “ON”, then an amplifier trouble condition has occurred. An amplifier trouble condition may be caused by: 1. A faulty SAA/SALL module. 2. A faulty Motherboard (SCMB). Perform the following: 1. Replace the SAA/SALL module. 2. Replace the Motherboard (SCMB).
Procedure I On the Single Circuit Mother Board (SCMB), the green NORMAL LED is “OFF”, the yellow TROUBLE LED is “ON”, and the MDX-2 SYSTEM NORMAL LED is “OFF”, SYSTEM TROUBLE LED is “ON”, and the TROUBLE LED is “OFF”, then the digital voice module may be completely inoperative. This condition is caused by: 1. 2. 3. 4. Too low input voltage on the digital voice module. Missing or improperly installed program memory EPROM. Broken TROUBLE LED (digital voice module is operative if this is the cause).
3. Missing or improperly installed message memory EPROM's. 4. One or more of the messages were not programmed completely. 5. Failed circuitry on the MDX-2. If the error was due to one of the first four causes, the trouble will clear automatically when the cause is corrected. The first four causes should only occur when power is first turned on to the Series MDX-2. When a message memory error is indicated, perform the following: 1.
5. Remove the malfunctioning module(s) and install the replacement module(s). Perform all checkout procedures described in the “Installation” section of this manual to make sure the replacement module(s) is (is) operating properly. Section 7-3 – Single Circuit SAFEPATH® Module Wiring Diagram Figure 7-4 on Page 7-13 illustrates the Single Circuit SAFEPATH® Module Wiring between modules. Note the wires are color-coded.
Resistor 10K Ohm 1/4W WHITE BLACK 120VAC INPUT DC+ DC- BAT FAIL J1 J2 AC FAIL AC AC WHITE BLACK + - BAT RED POWER SUPPLY XFMR 10 6 WHITE 4 2 BLACK 6 2 4 XFMR 10 7-13 12 10 7 8 7 8 TB1 A83413 MDX-2 TB3 WHITE YELLOW ORANGE Figure 7-4 Single-Circuit SAFEPATH Module Wiring Diagram BLACK RED BLACK BLACK BLACK 1 2 RED BLACK BLUE CH PLAY + LINE IN + LINE OUT + TB4 24V+ 24V- SCMB TB2 DV POWER + DV POWER DV STATUS +
Intentionally Blank 7-14
Chapter 8 Technical Data Section 8-1- Mechanical Dimensions (H x W x D) 21 x 16 x 6 in. Weight 40 lb. Finish Red Enclosure Construction Type 0.
Outputs Visual Notification Appliance Output 1 output circuit. 2.0 amps at 24VDC per zone. Supervised. Central Amplified Audio Output 1 output circuit. Selectable 25, 70.7 volt output at 40W or 80W max, or 100 volt (export) at 80W. (Depending on amplifier configuration). Supervised. Amplified Speaker Audio Output 1 output circuit, 15 Ohms, Amplified Speaker Power Output 1 output circuit. 2.0 amps at 24VDC (when configured with a SALL-15S). Supervised. Trouble Audible Output 0.100 amps at 24VDC.
End-of-Line Resistor Visual Notification Appliance Outputs UL LISTED 10K Ohm, 1/8W Minimum ±5% Audio Notification Appliance Outputs UL LISTED 10K Ohm, 1W Minimum ±5% Amplified Speaker Appliance Power Outputs UL LISTED 10K Ohm, 1W Minimum ±5% NOTE: A package of 8 UL LISTED 10K Ohm, 1W resistors are available through Wheelock, Inc. Model Number EOLK (Part# 5076).
Intentionally Blank 8-4
Chapter 9 - Module Descriptions Section 9-1 - Introduction There are ten modules in the Single Circuit SAFEPATH® Panel product line. The ten modules are: 1. Single Circuit Mother Board (SCMB) 2. Digital Voice Module (MDX-2) 3. Power Supply / Battery Charger (DCPS) 4. Supervised Audio System Amplifier/Signal Circuit Module (SAA-40S) 5. Supervised Audio System Amplifier/Signal Circuit Module (SAA-80S/SE*) 6. Supervised Audio Line Level Module (SALL-15S) 7. Speaker Circuit Splitter (4 way) (SC-SPL) 8.
Location of Plug-In Modules The interior view of the Single Circuit SAFEPATH Panel with the modules is shown in Figure 9-1. The amplifier modules may be used in any combination by installing into slots 1 and 2 in the DCMB. Also Figure 9-1 shows the locations of the MDX-2, Power Supply, Amplifier Module, and the SC-SPL. The Power Supply is mounted under the Digital Voice Module (MDX-2). The SC-SPL is mounted on the dead front panel.
Section 9-2 - Single Circuit Mother Board (SCMB) Wheelock, Inc. Part Number 108974 The Single Circuit Mother Board provides all signal handling capabilities between itself and the amplifier modules, terminal blocks for output wiring, and connectors for handling signals from the digital voice module. The Single Circuit Mother Board is illustrated in Figure 9-2 on Page 9-5. A single amplifier module is connected to the SCMB. A single channel from the Digital Voice Module (MDX-2) is connected to the SCMB.
Nominal Specifications: Input Voltage Range 20 to 28VDC Supply Current (Idle) at 24VDC 75mA Supply Current (Full Load) at 24VDC 150mA Operating Temperature Range 0 to 49 Degrees C (32-120 Degrees F) Humidity Range 0 to 85%, Non-condensing 9-4
D1 D2 AMBER GREEN SAFEPATH P83167 REV B T1 F1 F1 TROUBLE AUDIO + TRB AUD K2 K1 SW1 SW2 K3 - SW3 U1 TRB COM TRB NO TRB NC ALARM COM ALARM NO TB1 ALARM NC + F2 DV POWER - + DV STATUS +LINE OUT + -LINE IN U2 +CH PLAY U4 U3 F2 REMOTE MICROPHONE STATION POWER TB2 + -RM AUDIO X1 RM TXD RM RXD X2 + TB3 U5 RM POWER - 1 2 3 4 SW4 RM ENABLE SYNC DV ENABLE LAMP TEST 3 4 ON TONE SEL 3 2 1 GND FLT ENB 1 C16 2 U6 ON SW5 E1 J1 GROUND CONNECTION R53 GROUND FAULT ADJ
Section 9-3 - Digital Voice Module (MDX-2) Wheelock, Inc. Part Number: 105094 The Digital Voice Module (MDX-2) provides playback capability of pre-recorded messages. The MDX-2, when activated, provides a pre-recorded tone and/or message to the Single Circuit SAFEPATH® Panel which then broadcasts it through the amplifiers and to the audio appliances. The MDX-2 can have up to 8 pre-recorded messages that can be initiated by dry contact closure or open collector for each one.
9-7 NOTE: The MDX-2 Module is mounted upside down in the Single Circuit SAFEPATH® Panel to allow access to the terminal blocks. Figure 9-3 shows this module as it is mounted.
Section 9-4 - Power Supply / Battery Charger (DCPS) Wheelock, Inc. Part Number: 107378 The Power Supply / Battery Charger (Figure 9-4) provides the Single Circuit SAFEPATH® Panel with a power supply/battery charger with an output of 24VDC with a maximum current of 6 Amps. The battery charger section is capable of charging a 40 AH battery in 48 hours. The Power Supply is protected with short circuit protection and thermal shutdown.
Section 9-5 - Supervised Audio System Amplifier/Signal Circuit Module, 40 Watts (SAA-40S) Wheelock, Inc. Part Number: 105493 The supervised audio system amplifier/signal circuit module, 40 watts (SAA) provides audio amplification for the SAFEPATH® system. The amplifier can be selected to have either a 25V or a 70.7V audio output. The amplifier contains a switch mode power supply, a linear amplifier, and supervision circuitry.
Strobe Trouble LED Fuse F2 - Strobe Power. 3 Amp. Audio Trouble LED Amplifier Trouble LED Switch S1 - 25V / 70.7 V Speaker Selector Switch Fuse F1 - Main Amplifier Fuse. 10 Amp.
Section 9-6 - Supervised Audio System Amplifier/Signal Circuit Module, 80 Watts (SAA-80S/SE) Wheelock, Inc. Part Number: SAA-80S 105495, SAA-80SE 105496 The supervised audio system amplifier/signal circuit module, 80 watts (SAA) provides audio amplification for the SAFEPATH® system. The amplifier can be selected to have either a 25V or a 70.7V audio output. The SAA-80SE (European version) is 100V audio output only.
Strobe Trouble LED Fuse F2 - Strobe Power. 3 Amp. Audio Trouble LED Amplifier Trouble LED Switch S1 - 25V / 70.7 V Speaker Selector Switch (SAA-80S Only) SAA-80SE Switch is Removed. (100 V Only) Fuse F1 - Main Amplifier Fuse. 10 Amp.
Section 9-7 - Supervised Audio Line Level Module (SALL-15S) Wheelock, Inc. Part Number: 105497 The Supervised Audio Line Level Module (SALL-15S) provides audio output for the SAFEPATH system. The circuit module has a 0.5Vrms, 15 ohm audio NAC circuit, a 24VDC, 2A speaker amplifier power output, and a 24VDC, 2A strobe NAC Circuit. The circuit module contains a linear amplifier and supervision circuitry.
C 16 C 15 C 14 R 46 U5 R 43 R 44 R 45 R 42 C 13 C 12 C 11 P 82757 REV.
Section 9-8 - Notification Appliance Circuit Interface Module (NACIM) Wheelock, Inc. Part Number: 105498 The Notification Appliance Circuit Interface Module (NACIM) in Figure 9-8 is used to convert the Notification Appliance Circuit (NAC) of a Fire Alarm Control Panel (FACP) to an open collector circuit to operate the inputs of the Digital Voice Module. The NACIM can be connected to either a 12-volt or a 24volt NAC circuit.
Section 9-9 - FOUR ZONE SPLITTER (SC-SPL) Wheelock, Inc. Part Number: SC-SPL-B (Black) 107367, SC-SPL-R (Red) 107368 The Four Zone Splitter (SC-SPL) in Figure 9-9 is designed to be used with Wheelock’s Single Circuit SAFEPATH® Panels and provides a means for expanding a supervised audio output zone from one to four sub zones. The Four Zone Splitters are UL Listed under UL Standard 864, Control Units for Fire Protective Signaling Systems. They are listed for indoor use only.
Section 9-10 - Auxiliary Input Module (AIM-3) Wheelock, Inc. Part Number: 107387 The Auxiliary Input Module (AIM-3) is an outboard module for use with the SAFEPATH® Panels to expand the number of optional Remote Microphone Stations from one to three. It also has the capability of using one of the Remote Microphone Inputs to connect to a telephone system page port. See Figure 9-10 on Page 9-18. Additional information is available on the AIM-3 Installation Instruction Sheet P83667.
A83640 AUDIO INPUT MODULE AIM-3 P83639 REV. B 3 2 1 OFF ON ON SW1 + _ AUDIO TXD RXD F1 + _ + _ F2 + _ POWER + _ AUDIO 2 + _ + _ 1 POWER AUDIO TXD RXD/CC PHONE RM AUDIO TXD RXD .1 AMP SW2 POWER TXD RXD .1 AMP + _ POWER/CC .
Section 9-11 - Remote Microphone Station (RMS-2) Wheelock, Inc. Part Number: RMS-2R (Red) 105475 The Remote Microphone Station (RMS-2) is designed to used with the Single Circuit SAFEPATH® Panel. It provides a means of emergency voice announcements from a remote location. Only 1 Remote Microphone Station connection is available on the SAFEPATH® Panel. A single RMS-2 module can be connected, or an Auxiliary Input Module (AIM-3) can be connected, allowing as many as three RMS-2 modules to be used.
Intentionally Blank 9-20
Chapter 10 - MEA and Warranty Recommendations - That the above units be accepted on condition that all uses, configurations, arrangements and functions, locations and installations comply with the New York City Building Code, specifically Subchapter 17 and with the Referenced Standard RS 17-3 through 17-3C including the NFPA as appropriate, the UL Listing, the manufacturer’s instructions, the Fire Department Rules and the Electrical Code of the City of New York, and on further condition that: (a) The use,
Limited Warranty Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated, maintained and operationally tested in accordance with these instructions at the time of installation and at least twice a year or more often and in accordance with local, state and federal codes, regulations and laws.
BATTERY BACKUP CALCULATION WORKSHEET Tables for thisworksheet are in Section 3-5 of this manual. STANDBY CURRENT CALCULATIONS 1. Select and record Standby Current for Model from Table 3-4. 2. Select Standby Current for Optional Modules from Table 3-5. List them in Table 1. Module Table 1 Standby Qty Current Qty X Standby Current 3. Calculate total Standby Current from Table 1. 4. Add Standby Current from Step 1 and Step 3. 5. Multiply results of Step 3 by the number of hours of Standby required.
2. Using Table 2, calculate total STROBE CURRENT. 3. For SAA Series Amplifier Modules, use Table 2 and calculate total SPEAKER WATTAGE. 4. For SALL-15S Module, use Table 2 and calculate total "SPKR AMP" current. 5. SAA Series Modules,calculate the Alarm Current Module using the total SPEAKER WATTAGE from Step 3 and Table 3-7 in this manual. 6. In Table 3, using Table 3-5, list all alarm currents of Modules installed. Table 3 Module SCSP-PS MDX-2 Qty Alarm Current 1 0.150 1 0.090 Total Alarm Current 0.