Instruction manual

8-2
! Warnin
g:
Outputs
Visual Notification Appliance
Output
1 output circuit. 2.0 amps
@ 24 VDC per zone.
Supervised.
Central Amplified Audio Output 1 output circuit.
Selectable 25, 70.7volt
output at 40W or 80W max,
or 100v (export) at 80W
max. (Depending on
amplifier configuration), per
zone. Supervised.
Amplified
10K
Ohms Speaker
Audio Output
1 output circuit, 15 Ohms,
-5dBm output max (when
configured with a SALL-
15S), per zone. Supervised
Amplified Speaker Power
Output
1 output circuit. 2.0 amps
@ 24 VDC (when
configured with a SALL-
15S), per zone. Supervised.
Trouble Audible Output 0.100 amps @ 24 VDC.
Non-Supervised.
Status Contact Form C contact normally
energized. Contacts
transfer during trouble: 0.5
amps @ 24 VDC max,
resistive load (see following
warning). Non-Supervised.
Alarm Contact Form C contact normally
de-energized. Contact
transfers during alarm: 0.5
amps @ 24 VDC max,
resistive load (see following
warning). Non-Supervised.
Table 8-1 Outputs
DO NOT EXCEED THE RATINGS OF THE STATUS CONTACTS.
EXCEEDING THIS RATING MAY CAUSE THE RELAY TO FAIL AND
PREVENT A TROUBLE CONDITION FROM BEING INDICATED.
DO NOT EXCEED THE RATINGS OF THE ALARM CONTACTS.
EXCEEDING THIS RATING MAY CAUSE THE RELAY TO FAIL AND
PREVENT THE MESSAGES FROM BEING PLAYED.