Instruction manual

5-3
NOTE:
Acknowledging a trouble condition silences the internal sounder and any external trouble
signaling devices. The system will remain in the trouble condition with the yellow
“TROUBLE” light on. The system trouble contact will remain in the trouble position until
all trouble conditions have been corrected. Any faults, which occur after
acknowledgment, will resound the trouble circuit.
selected for announcements.
Each zone's "SELECT" LED indicates that zone has been
To select all zones at once, set the ALL-CALL switch
ANY ZONE SWITCH SET IN THE "OFF" POSITION WILL SI LENCE IT'S
RESPECTIVE ZONE.
2. Deliver message. Activation of the microphone will
press the push-to-talk switch on microphone.
1. Hold the microphone within 2 inches of mouth and
trouble signaling devices. The system will remain in the
position until all trouble conditions have been corrected.
and the system trouble contact will remain in the trouble
trouble condition with the yellow "TROUBLE" LED on
This will only silence the internal sounder and any external
1. Momentarily depress the TROUBLE ACKNOWLEDGE button.
CONTACT YOUR SERVICE REPRESENTATIVE IMMEDIATELY.
OTHERS. IN THE EVENT THE "TROUBLE" LIGHT IS ON, YOU SHOULD
IN PROPERTY DAMAGE, SERIOUS INJURY OR DEATH TO YOU AND/OR
PROVIDE EMERGENCY ANNOUNCEMENT CAPABILITIES AND COULD RESULT
IF THE YELLOW "TROUBLE" LIGHT IS ON, THIS UNIT MAY NOT BE ABLE TO
FAULT in the system which MUST BE CORRECTED.
When the YELLOW "TROUBLE" LED is ON there is a
When the GREEN "NORMAL" LED is ON, the system
1. Slide the AUTOMATIC/MANUAL switch DOWN to the
Refer to OPERATION & INSTALLATION MANUAL.
FOR ADDITIONAL INFORMATION:
WARNING
ZONE SELECTION
to the ON position.
deliver the message to all circuits.
MICROPHONE OPERATION
To Sound Evacuation Tone:
MANUAL position.
MANUAL OPERATION
ACKNOWLEDGEMENT
To Acknowledge a Trouble Condition:
WARNING
is functioning properly.
AUTOMATIC
ACKNOWLEDGE
TROUBLE
MANUAL
RESULT IN DAMAGE TO THE PC BOARDS.
- FIRST DISCONNECT
POWER AT THE POWER SOURCE, THEN
RECONNECT BATTERY POWER AT THE BATTERY
- FIRST RECONNECT AC
THEN DISCONNECT AC POWER AT THE
BATTERY POWER AT THE BATTERY TERMINALS,
TERMINALS.
POWER SOURCE.
RECONNECTING
DISCONNECTING
BEFORE REMOVING THIS PANEL:
THIS UNIT FIRST. FAILURE TO DO SO MAY
MODULAR PC BOARDS INSIDE WITHOUT
DISCONNECTING ALL POWER SOURCES TO
DO NOT ATTEMPT TO REMOVE OR REPLACE
CAUTION
PLACE
MIC
HERE
ON
OFF
SELECT
SELECT ALARM
TROUBLE
NORMAL
ON
OFF
To select zones individually for live announcements,
set each desired zone switch to the ON position.
Each zone's "ALARM" LED indicates that zone is active.
RESET
RESET
To Turn Off Strobes:
1. All initiating circuits must be reset.
2. Momentarily depress the RESET button.
MAIN
ALL-
CALL
ZONE
1
SELECT
ALARM
ON
OFF
ZONE
1
Figure 5-1
Dual-Circuit SAFEPATH
®