Instruction manual
5-2
Section 5-2 - To Make Live Announcements
From Panel
1. Select Zones or use “ALL-CALL” for all zones. See Figure 5-1 for switch locations.
2. Hold the microphone within 2 inches of your mouth, press push-to-talk switch and
begin speaking.
From Optional Remote Microphone Station (RMS-3)
1. Turn the key switch from the OFF position to the ON position.
2. Select Zones or use “ALL-CALL” for both zones. (See Figure 3 in Appendix B)
3. Hold the microphone within 2 inches of your mouth, press push-to-talk switch and
begin speaking.
See the Remote Microphone Station instruction sheet or Appendix B for additional information.
Section 5-3 - To Sound Evacuation Tone
From Panel
1. Slide the “AUTO/MANUAL” switch on the panel down to the MANUAL position. The
selected tone will play. Turn off the tone by returning the AUTOMATIC/MANUAL
Switch to the UP position. See Figure 5-1 on Page 5-3 for switch location. All zones
will be selected.
From Optional Remote Microphone Station (RMS-3)
1. Turn the key switch from the “OFF” position to the “ON” position.
2. Slide the “AUTO/MANUAL” switch down to the MANUAL position. The selected
tone will play. Turn off the tone by returning the AUTOMATIC/MANUAL Switch to
the UP position. See Figure 5-1 on Page 5-3 for switch location.
See the Remote Microphone Station instruction sheet for additional information.
Automatic Operation
1. With the Digital Voice Module installed, the contact closure inputs IN1 through IN8 on
the Mother Board initiate files 1 through 8 on the digital voice module respectively.
2. If the Digital Voice Module is not installed and the Shunt PCB (See Figure 3-19 on
Page 3-20) is in its place, the contact closure inputs IN1 and IN2 initiate zones 1 and
2 respectively and play the tone selected on the Control Module (DCDC).
Section 5-4 - To Reset Visual Appliances
1. All activation inputs must be cleared.
2. Momentarily depress the “RESET” pushbutton. See Figure 5-1 on Page 5-3 for
pushbutton location.
Section 5-5 - To Acknowledge a Trouble Condition
1. Momentarily depress the “TROUBLE ACKNOWLEDGE” pushbutton. See Figure 5-1
on Page 5-3 for pushbutton location.