Instruction manual
4-2
! Warnin
g:
MESSAGES REQUESTED BEFORE AND DURING A TROUBLE
CONDITION MAY NOT BE HEARD, WHICH COULD RESULT IN
PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU
AND/OR OTHERS. IF MESSAGES REQUESTED BEFORE AND DURING
A TROUBLE CONDITION ARE STILL NECESSARY, THEY SHOULD BE
REPEATED WHEN THE SAFEPATH
®
PANEL IS RETURNED TO
NORMAL.
Visual Notification Appliance Output Circuit Supervision
The visual notification appliance output circuit is supervised for open and short circuits when the
SAFEPATH
®
Panel is in Standby mode. Output circuit supervision requires installation of the
supplied UL LISTED, 10K Ohm EOLR resistor on the NAC circuit. Any sensed trouble will
illuminate the “STR” LED on the amplifier module. See Figure 3-18 for LED location.
Audio Notification Appliance Output Circuit Supervision
The audio notification appliance output circuit is supervised for open and short circuits when the
SAFEPATH
®
Panel is in Standby mode. Output circuit supervision requires installation of the
supplied UL LISTED, 10K Ohm EOLR resistor on the output circuit. Any sensed trouble will
illuminate the “SPK” LED on the amplifier module. See Figure 3-18 for LED location.
Amplified Speaker Notification Appliance Power Output Circuit Supervision
The amplified speaker notification appliance power output circuit supervised for open and short
circuits SAFEPATH
®
Panel is in Standby mode. Output circuit supervision requires installation of
the supplied UL LISTED, 10K Ohm EOLR resistor on the output circuit. Any sensed trouble will
illuminate the “PWR” LED on the SALL-15S module. See Figure 3-18 for LED location.
Amplifier Supervision
A supervisory tone plays through the amplifier during standby for supervision purpose. Any
sensed trouble illuminates the “AMP” LED on the amplifier module. See Figure 3-18 for LED
location.
Remote Microphone Supervision (Optional RMS-3)
The audio circuit is supervised on the Remote Microphone Station circuit board.