Instruction manual

3-26
Table 3-5
Standby and Alarm Current for Dual-Circuit
SAFEPATH
®
Modules
SAFEPATH
Module
Standby Current Alarm Current
DCSP-PS
4
0.150
0.150
MDX-2 0.070 0.090
SPL 0.040 0.190
AIM-3 0.040 0.060
RAM-1 0.000 0.050
RMS-3
0.040 0.060
5
NACIM 0.000 0.007
4
Current draw with no amplifier and no Digital Voice Module installed.
5
Current during RMS-3 page is 0.060 Amps. Current during telephone page is 0.100 Amps.
Table 3-6
Standby Current for Dual-Circuit
SAFEPATH
®
Amplifier Modules
Amplifier Module
6
Standby Current per
UL Full Power SIN
Wave Testing
Standby Current
when DCDC is in
Temporal Code 3
Tone
Standby Current
when DCDC is in
HI/LO (Worst Case
Tone)
SAA-40S 0.400 0.300 0.300
SAA-80S/SE 0.600 0.300 0.400
SALL-15S
7
0.100 0.100 0.100
6
Maximum strobe current on each amplifier in the panel is 2 Amps.
7
Maximum “SPKR AMP” current on each SALL-15S Module is 2 Amps at 24 VDC.
Alarm Current
Table 3-5 lists the alarm current of the Dual-Circuit SAFEPATH
®
Modules. Table 3-7 on Page 3-
27 lists the alarm current for each amplifier. If no amplifiers are installed in the amplifier slot the
current for that slot is zero.
If no strobes are installed in the zone, the current is zero. If strobes are installed, add the sum of
the current ratings of the strobe in each circuit to the corresponding amplifier.
UL alarm speaker current calculations are measured with a full SIN wave input with a maximum
output are as follows:
Alarm Current Calculating Procedure
1. Using Table 3-7 on Page 3-27, calculate the alarm current for each amplifier module
installed.
2. Using Table 3-5, add up the alarm currents of all optional modules. If multiple RMS-3 with
an AIM-3, calculate the alarm current for one. If SPL and/or NACIM Modules are used,
calculate the alarm current for each one.
3. Add together the strobe current from both amplifier NAC circuits.
4. Total the results of Steps 1 through 3.