Instruction manual
3-23
Testing all connections to equipment that is interconnected with the SAFEPATH
Panel.
ALL PROTECTIVE SIGNALING SYSTEMS REQUIRE PERIODIC TESTING.
ALL PROTECTIVE SIGNALING SYSTEM EQUIPMENT SHALL BE TESTED
BY QUALIFIED PERSONNEL AT LEAST TWICE A YEAR FOR PROPER
OPERATION, OR MORE OFTEN IF REQUIRED BY CODES, REGULATIONS
AND LAWS. FAILURE TO MAINTAIN AND TEST PROTECTIVE
SIGNALING SYSTEM EQUIPMENT CAN RESULT IN NOT DETECTING
EQUIPMENT FAILURE THAT CAN CAUSE PROPERTY DAMAGE AND
SERIOUS PERSONAL INJURY OR DEATH TO YOU AND/OR OTHERS
DURING AN EMERGENCY SITUATION.
Section 3-7 - Battery Care and Backup Battery Calculations
Installation and Care of Sealed Lead Acid Batteries
Sealed lead acid batteries are designed to operate in standby service for approximately five
years. This is based upon a normal service condition where there is an ambient temperature of
20 degrees C (68 degrees F) and batteries are completely discharged once every three months.
LENGTH OF SERVICE LIFE WILL BE DIRECTLY AFFECTED BY THE NUMBER OF
DISCHARGE CYCLES, DEPTH OF DISCHARGE, AND AMBIENT TEMPERATURE.
Use Guidelines:
Avoid installation and/or operation in close proximity to heat sources. While the operating
temperature range is 0 to 49 degrees C (32-120 degrees F), battery life will be maximized at an
ambient temperature of 20 degrees C (68 degrees F).
Batteries may generate ignitable gases. Because of this, batteries shall be installed in a well-
ventilated location, away from spark producing equipment.
Batteries shall not be installed in an atmosphere where organic solvents or adhesives may be
present. The batteries shall not be cleaned with oils, thinners, or similar substances. The case
and cover of the batteries are ABS plastic resin, which may suffer damage from these chemicals.
Batteries shall not be installed in a heavy vibration or shock location.
Batteries shall have a minimum of ¼” separation between cells.
Insulated gloves shall always be worn when handling batteries.
BATTERIES SHALL NOT BE CRUSHED, INCINERATED, OR
DISMANTLED. THE ELECTROLYTE CONTAINS SULFURIC ACID, WHICH
CAN CAUSE SERIOUS DAMAGE TO EYES AND SKIN. IF CONTACT
DOES OCCUR, FLUSH WITH WATER AND SEEK IMMEDIATE MEDICAL
ATTENTION.
Batteries of different capacities, age, or manufacturer shall not be used together.
Battery Storage
Batteries which are to be stored for an extended period of time should be given a supplement
charge monthly. Batteries should never be stored in a discharged condition.
! Warnin
g:
! Warnin
g: