Instruction manual

3-22
Amplifiers (SAA-40S, SAA-80S, 80SE, SALL-15S)
SAA-40S, SAA-80S, 80SE
LED D15 (STR) “OFF”
LED D10 (SPK) “OFF”
LED D6 (AMP) “OFF”
SALL-15S
LED D16 (STROBE) “OFF”
LED D13 (AUDIO) “OFF”
LED D10 (PWR) “OFF”
LED D3 (AMP) “OFF”
3. Play all messages by momentarily shorting IN1 through IN8 on Mother Board. (See Figure 3-11
on Page 3-12 for location.)
Control Module: Right (RED) LEDs D4 and D5 “ON”. (Figure 3-18)
Messages will broadcast on all appliance circuits. If Strobe NAC circuits are in use,
Strobes will also flash. With SW9 DIP Switch SS in ON position (Figure 3-20 on Page 3-
20), relay on DCDC clicks at 1 click per second. When message ends, Strobes will stop
flashing and relay on DCDC will stop clicking.
Amplifier Module: All LEDs “OFF”
4. Key Microphone in panel for live voice test.
Control Module: Right (RED) LEDs D4 and D5 “ON”. If Strobe NAC circuits are in use,
Strobes will also flash. With SW9 DIP Switch SS in ON position (Figure 3-20 on Page 3-
20), relay on DCDC clicks at 1 click per second. When microphone button is released,
right LEDs D4 and D5 “OFF”, strobes and relay on DCDC will continue to operate.
Amplifier Module: All LEDs “OFF”
Press RESET button on DCDC. Strobes and Relay “OFF”
5. Press MAIN (Auto/Manual) Switch to the DOWN position.
Control Module (DCDC): Right (RED) LEDs D4 and D5 “ON”. If Strobe NAC circuits are in
use, Strobes will also flash. With SW9 DIP Switch SS in ON position (Figure 3-20 on Page
3-20), relay on DCDC clicks at 1 click per second. Return MAIN Switch to the UP position,
right LEDs D4 and D5 “OFF”, strobes and relay on DCDC will continue to operate. (See
Figure 3-18)
Amplifier Modules: All LEDs “OFF”.
Press RESET button on DCDC Relay will stop clicking. (See Figure 3-18 on Page 3-18).
6. If Remote Microphone Station (RMS-3) is included, enable it by switching SW9-1 (RM) DIP
Switch to “ON” on the Dual-Circuit Control Module (DCDC). (See Figure 3-20 on Page 3-20)
7. Test the Remote Microphone Station.
8. Turn “OFF” ALL CALL, and ZONE 1 and ZONE 2 Switches. On the DCDC Module, all
LEDs should be “OFF” except the NORMAL (Green) LED. (Figure 3-18 on Page 3-18)
9. System is fully operational.
Additional system checkout should include:
Testing all Alarm and Trouble circuits.