Instruction manual

3-21
Table 3-2
DCDC DIP Switch Setting Description
DCDC DIP Switch SETTING/DESCRIPTION
SW9 Position 1 (RM) REMOTE MICROPHONE ENABLE. “ON” enables optional
Remote Microphone Station. “OFF” disables Remote Microphone
Station circuit.
SW9 Position 2, (SS)
SYNCHRONIZED STROBES ENABLE. “ON” enables Strobe NAC
to work with Wheelock’s synchronized strobes.
SW9 Position 3, (RS) Remote SAFEPATH
®
ENABLE. Leave in “OFF” position. (Used only
with Remote SAFEPATH
®
Panel and when Digital Voice Message
has the highest priority.)
SW9 Position 4, (F1) Leave in “OFF” position
SW10 Position 1, (F2) Leave in “OFF” position.
SW10 Positions 2, 3, &
4, (T1, T2, & T3)
MULTITONE SELECT. Selects 1 of 8 tones used for the primary
evacuation signal. Use chart below to select the tone.
Table 3-3
DIP Switch Settings for Available Tone Sounds
SWITCH SETTINGS FOR AVAILABLE TONE SOUNDS
TONE SOUND
SW10-2
T1
SW10-3
T2
SW10-4
T3
Horn (Continuous) ON ON ON
Bell (1560 Hz Modulated) ON OFF ON
March Time Horn (.25 Sec ON, .25 Sec OFF) OFF OFF ON
Code-3 Horn (ANSI S3.41 Temporal) ON ON OFF
Code-3 Tone 500Hz (ANSI S3.41 Temporal) OFF ON ON
Slow Whoop (500-1200Hz Sweep) OFF ON OFF
Siren (600-1200 Hz Sweep) ON OFF OFF
HI/LO (1000/800 Hz) OFF OFF OFF
2. Connect AC Power and Battery Backup.
3. Observe the following indicators: (See Figure 3-18 on Page 3-18 for LED locations)
Dual-Circuit Control Module (DCDC)
ALL CALL “Select” LED (Single Red) “ON”
All Dual Red LEDs left “ON”, right “OFF”
TROUBLE / NORMAL LEDs (Dual) Yellow “OFF”, Green “ON”
LEDs D10, D11, and D12 “OFF”
Digital Voice Module (MDX-2)
LED D1 (Green) “ON”
LED D2 (Yellow) “OFF”
LED D3 (Yellow) “OFF”