Section 3-6 System Checkout
Refer to NFPA 72 (1999 Edition) for guidelines on testing notification systems.
If a malfunction, or system trouble occurs during testing, STOP TESTING.
Correct the problem before you resume testing.
Insure that speaker and strobe NAC Circuits are not connected to the SAFEPATH
®
Panel
and that 10K Ohm, ¼ W, EOLR test resistors are connected in their place on the Mother
Board.
1. Place switches on the Dual-Circuit Control Module (DCDC) as follows (See Figure 3-20 for
enlarged view of DIP Switches):
DIP Switch SW10: T3 – OFF, T2 – ON, T1 – ON, F2 – OFF
(See Figure 3-20)
DIP Switch SW9: F1 – ON, RS – OFF, SS – ON, RM – OFF
(See Figure 3-20)
MAIN (Automatic / Manual) Switch: UP or “AUTOMATIC” position.
“ALL CALL” Switch, UP or “ON” position. (See Figure 3-18)
ZONE 1 and ZONE 2 Switches: UP or “ON” position. (See Figure 3-18)
Connect the AC power source before connecting the battery backup power.
Disconnect the battery backup power before disconnecting the AC power
source
.
2. Connect AC Power, then connect battery backup.
The green system normal LED indicator should be “ON’ to indicate normal operation. If the
amber system trouble LED is “ON”, a trouble condition is indicated. Refer to Chapter 7
"Troubleshooting and Servicing" to diagnose and correct the trouble condition.
Initial Checkout
3. With both AC Power and battery backup power applied observe the following indicators (See
Figure 3-18 on Page 3-18 for LED locations):
Dual-Circuit Control Module (DCDC)
ALL CALL “Select” LED (Single Red) “ON”
All Dual Red LEDs left “ON”, right “OFF”
TROUBLE / NORMAL LEDs (Dual) Yellow “OFF”, Green “ON”
LEDs D10, D11, and D12 “OFF”
Digital Voice Module (MDX-2)
LED D5 (Green) “ON”
LED D6 (Yellow) “OFF”
LED D7 (Yellow) “OFF”
Amplifiers (SAA-40S, SAA-80S,80SE, SALL-15S)
SAA-40S, SAA-80S/80SE
LED D15 (STR) “OFF”
LED D10 (SPK) “OFF”
LED D6 (AMP) “OFF”
SALL-15S
LED D16 (STROBE) “OFF”
LED D13 (AUDIO) “OFF”