Instruction manual

3-16
Procedure
1. See Figure 3-17 on Page 3-16 for SAFEPATH
®
Panel mounting hole layout.
2. Remove Amplifier Module(s), Digital Voice Module, and Control Module from the
enclosure.
3. Mark and drill mounting holes for appropriate screws and anchors to ensure secure mounting
to the type of surface at the selected location.
4. Prevent dust and dirt contamination of the SAFEPATH
®
Panel during installation. This
contamination can interfere with the operation and reduce the life of the equipment.
5. Open the door and mount the SAFEPATH
®
Panel at the selected location. Use care to
avoid damage to the module PC boards during installation. Do not apply excessive
pressure to any PC board or its components, including field wiring terminals and connectors.
6. Replace Amplifier Module(s), Digital Voice Module, and Control Module. Plug in Microphone.
7. For SAA-40S, 80S Amplifier Module, set 25V / 70V Switch to correct setting for speakers.
(See Figure 3-18 on Page 3-18)
17.00"
14.00"
Conduit Entrances (Top and Bottom)
Ground
Terminals
Figure 3-17
Dual-Circuit SAFEPATH
®
Panel Mounting