Instruction manual

3-15
! Caution:
POWER CONNECTION REQUIREMENTS
The Dual-Circuit SAFEPATH
®
Panel contains a 24VDC, 6 Amp Power Supply and a Battery Charger
for the battery backup. Connections for the input power and batteries are shown in Figure 3-16.
Calculate proper backup battery requirements using Section 3-7 on Page 3-23.
+
-
+
-
+
-
REMOTE
MICROPHONE
SPL
ALL CALL
PWR
AUDIO
TXD
RXD
LT
ALARM
TRBL
GND
P83459 REV.
DCSP MOTHER BOARD
J4
J2
J1
10
6
10
6
Power Supply and
Battery Charger
Battery Connection
Terminals
BAT
+
-
DC
BAT
+
-
SW1
AC
AC
AC
+
-
DC
SW2
BAT FAIL
NO NC C
AC FAIL
C NC NO
SMP7PM
120 VAC 60Hz.
Figure 3-16
Input Power and Battery Connection Locations
Section 3-5 - Mounting
Location
The SAFEPATH
®
Panel shall be mounted in a location within the environmental limits specified in
the latest UL Standard 864 for indoor control panels. The SAFEPATH
®
Panel shall not be located
in a hazardous area.
In order to comply with the latest NFPA and UL requirements for
interconnection of fire alarm control equipment, the SAFEPATH
®
Panel shall
be located in the same room, and within 20 feet of, a UL LISTED compatible
fire alarm control panel. Wiring shall be enclosed in conduit and properly
connected to such control panel.