Instruction manual
3-12
! Warnin
g:
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
CONTACT
CLOSURE
INPUTS
RS
232
COM
TD
RD
NC
IN8
IN7
IN6
IN5
IN4
IN3
IN2
IN1
P83459 REV.
DCSP MOTHER BOARD
Dry Contact Inputs
Figure 3-11
Dry Contact Input Connections
• The dry contact input meets the requirements for power limited fire protective signaling
circuits as defined in the National Electrical Code (NFPA-72). The dry contact inputs are not
supervised. If supervision is required, use Model Number NACIM (Notification Appliance
Circuit Interface Module)
• The field wiring for the dry contact input shall not exceed 100 Ohms of resistance or 0.050 µF
of capacitance.
• IN1 through IN8 are the contact closure inputs for as many as 8 separate messages.
• The RS-232 input terminals shown in Figure 3-11 are not used.
IT IS IMPORTANT THAT THE WIRING USED FOR INPUT VOLTAGE
WIRING IS LARGE ENOUGH TO CARRY THE MAXIMUM CURRENT
REQUIRED BY THE DUAL-CIRCUIT SAFEPATH
PANEL WITHOUT
EXCESSIVE VOLTAGE DROP. IF VOLTAGE DROPS FROM AC POWER
LINE LOADING AND WIRING RESISTANCE IS NOT WITHIN THE
SPECIFIED OPERATING VOLTAGE RANGE, THE SAFEPATH
PANEL
WILL NOT FUNCTION PROPERLY.
ALARM STATUS OUTPUT CONTACT WIRING
The location of the Alarm Status output connections are shown in Figure 3-10 Section C. A
magnified view of this area on the Mother Board is shown in Figure 3-12 on Page 3-13.
• Wire gauge selection of the Alarm Status output contact wiring should involve
consideration of all factors including, wire loop length, maximum current capacity,
and maximum voltage drop allowable.
• The Alarm Status output contact is Form C, rated for 0.5 amps at 24 VDC,
resistive load.
• For terminal connection details of the Alarm Status output contact (shown in the
non-alarm mode) see Figure 3-13 on Page 3-13.