Instruction manual
2-2
• Self Amplified power output circuit wiring open and short conditions
• Microphone open condition
• Amplifier operation
• Selected optional evacuation signal
• Optional remote microphone station
• Digital Voice Module (MDX-2)
• Alarm input activation wiring
• Input voltage/low battery
• Built-in audible alert indicates any supervision loss
• Auxiliary trouble output for notification appliance connection
• Remote reporting via output contacts for system trouble or alarm activation.
• An internal 6 amp power supply/battery charger (DCPS)
Optional Features
• Remote Microphone Station (RMS-3) for live, emergency announcements.
• Programmed Message Kit (PMK) for up to two minutes of messages tailored to customer’s
needs.
• Four Zone Audio Splitter (SPL) (maximum of two)
• Auxiliary Input Module (AIM-3) used to connect three Remote Microphone Stations or two
Remote Microphone Stations and a telephone page input.
• Redundant Amplifier Module (RAM-1)
CONTROL
SYSTEM
120 VAC
REMOTE
MICROPHONE
(RMS-3)
BATTERY
STANDBY
SAFEPATH
PANEL
SPEAKER CIRCUIT
STROBE CIRCUIT
SPEAKER CIRCUIT
STROBE CIRCUIT
INPUTS
TROUBLE
RELAY
8 STANDARD MESSAGES ON THE SMK OR
UP TO 2 MINUTES OF AUDIO STORAGE FOR
PERSONALIZED MESSAGES ON THE MDV-PMK.
UP TO 8 CONTACT ACTIVATIONS.
AMPLIFIED SPEAKER
(15 Ohms @ 0.5 VOLT AUDIO
24 VDC @ 2A MAX.)
24 VDC @ 2A Max.
CENTRAL AMPLIFIED
(40 OR 80 WATT, SELECTABLE
25V, 70.7V, or 100V)
Figure 2-1
Basic Capabilities of the Dual-Circuit SAFEPATH
®
Panel