Instruction manual

1-2
! Warnin
g:
! Warnin
g:
FOR PROPER OPERATION, THE SAFEPATH
PANEL SHALL BE
CONNECTED TO A LISTED COMPATIBLE AND PROPERLY
OPERATING CONTROL PANEL, WHICH CONTROLS ITS
ACTIVATION. ALL EQUIPMENT SHALL BE PROPERLY
INTERCONNECTED AND OPERATING. THE INSTALLER SHALL
CHECK COMPATIBILITY OF ALL EQUIPMENT PRIOR TO
INSTALLATION, OTHERWISE THE SAFEPATH
®
PANEL AND/OR
THE CONTROL PANEL MAY BE DAMAGED AND/OR FAIL TO
OPERATE IN AN EMERGENCY SITUATION.
Notification equipment cannot last forever. Even though SAFEPATH
®
Panel is expected to last
up to ten years, any of its parts or components could fail before then. Therefore testing of the
entire protective signaling system, including the SAFEPATH
®
panel, all notification equipment, as
well as all messages and their output channel, and priority assignment, shall be conducted at
least twice each year, or more often as required by local, state and federal codes, regulations and
laws, by qualified personnel. If the notification equipment is not working properly, immediately
contact the installer and have all/any problems corrected immediately. Malfunctioning
components should be replaced immediately. Do not attempt to repair malfunctioning
components. Malfunctioning components should be returned for factory repair or replacement.
In the event you cannot contact the installer, contact the manufacturer.
CERTAIN HARDWARE FUNCTIONS ON THE SAFEPATH
PANEL
ARE NOT SUPERVISED. IF ANY SUCH HARDWARE FUNCTIONS
FAIL, THE SAFEPATH
®
PANEL MAY NOT PROVIDE THE INTENDED
WARNING AND/OR NOT INDICATE A TROUBLE CONDITION. THE
FOLLOWING ARE NOT SUPERVISED:
1. THE "SHORT CIRCUIT" DETECTION CIRCUITRY FOR ANYONE
OR ALL OF THE EIGHT CONTACT INPUTS.
THE FOLLOWING HARDWARE FAILURES WOULD PREVENT THE
SAFEPATH
®
PANEL FROM INDICATING A TROUBLE CONDITION:
1. THE "OPEN CIRCUIT" DETECTION CIRCUITRY FOR ANY ONE OR
ALL OF THE EIGHT CONTACT INPUTS.
2. THE AUDIO SUPERVISION CIRCUITRY FOR EACH OF THE TWO
OUTPUT CHANNELS.
3. THE STATUS CONTACT.
THESE HARDWARE FUNCTIONS SHALL BE PERIODICALLY
CHECKED FOR PROPER OPERATION.
Section 1-3 -
Compliance with Applicable Codes, Regulations,
Laws, Standards, and Guidelines
COMPLY WITH ALL OF THE LATEST APPLICABLE CODES, REGULATIONS, LAWS,
STANDARDS, AND GUIDELINES.