Installation manual
SAFEPATH Manual Sheet 74 of 78
Rev. C April 1999
Digital Voice Module with Playback (DX-100)
The digital voice module (DX-100) controls the message playback in the SAFEPATH system. When a dry contact closure or a serial
port command initiates a file playing, the DX-100 signals the SADC to switch from the standby condition to an alarm condition for the
zone indicated.
The DX-100 can store up to 999 message files. Message files may be any combination of record or string files. Up to 8 minutes of
messages may be stored in the DX-100’s EPROM message memory.
Messages can be selected to play using a dry contact closure or a command on the serial port. Dry contacts may be connected
directly to the DX-100 or to a DV-EM connected to the DX-100, but not both. Up to eight files may be selected using the dry contact
inputs on the DX-100, up to 256 files may be selected using the dry contact inputs on up to eight optional DV-EM’s, or up to 999 files
may be selected using commands on the serial port.
There are two fuses on the printed circuit board, F1 and F2. Fuse F1 is the main fuse for the entire board. F2 is the fuse for output
channel 1. See Figure 38 for fuse locations.
Fuse Rating
F1 0.5A
F2 0.5A
Nominal Specifications:
Input Voltage Range 11 to 29VDC
Supply Current (Idle) @ 24VDC 186mA
Supply Current (Alarm) @ 24VDC 246mA
Operating Temperature Range 0 to 49 Degrees C (32-120 Degrees F)
Humidity Range 0 to 85%, Non-condensing
Figure 38.
Digital Voice Module with Playback