Installation manual
Remote SAFEPATH Manual Sheet 49 of 50
Rev. C December 1998
Technical Specifications
Mechanical
Dimensions (H x W x D) 36" by 24" x 6"
Weight 90 pounds
Enclosure 0.050" Steel
Finish Black
Mounting Indoor Surface Mount
Top and Bottom Wiring Entry
Environmental
(Meets UL requirements)
Operating Temperature 0° to +49° C (32 to 120 Degrees F)
Storage Temperature -20° to 70° C (-4 to 158 Degrees F)
Humidity 85±5% @ 30±2° C (86 ± 4 Degrees F) Non-condensing
Electrical
Input Voltage: 120VAC
Input Current (max): 8.0 at 120VAC
Outputs
Visual Notification 1 to 4 output channels optionally provided; each output is rated for
Appliance Output 2.0 Amps at 24V. Total of all output channels may not exceed 6.0 Amps.
Central Amplified 1 to 4 output channels optionally provided; each programmable for Audio
Output either 25V, 70.7V or 100V output.
Amplified Speaker 1 to 4 output channels optionally provided; each through 15 Ohm
Audio Output isolation transformer. Output level is -5 dBm maximum
Amplified Speaker 1 to 4 output channels optionally provided; each output is rated for
Power Output 2.0 Amps at 24V.
Trouble Audible Output is rated for 0.100 Amps at 24VDC
Output
Status Contact Form C contact normally energized. Contacts transfer during trouble.
Rated 0.5 Amps at 24VDC max, resistive load.
WARNING: DO NOT EXCEED THE RATINGS OF THE STATUS CONTACT. EXCEEDING THE RATINGS MAY CAUSE
THE RELAY TO FAIL AND PREVENT A TROUBLE CONDITION FROM BEING INDICATED.
Alarm Contact Form C contact normally de-energized. Contact transfers during alarm.
Rated 0.5 Amps at 24VDC max, resistive load.
WARNING: DO NOT EXCEED THE RATINGS OF THE ALARM CONTACT. EXCEEDING THE RATINGS MAY CAUSE
THE RELAY TO FAIL AND PREVENT MESSAGES FROM BEING PLAYED.
Wiring Connections
Screw Terminals Each terminal accepts one conductor from #22 to #12 AWG.
End-of-Line Resistor
Visual Notification
Appliance Outputs 10K, 1/8W Minimum, 5%
Audio Notification
Appliance Outputs 10K, 1W Minimum, 5%
Amplified Speaker
Appliance Power Outputs 10K, 1/8W Minimum, 5%
Limited Warranty
Wheelock products must be used within their published specifications and must be PROPERLY specified, applied,
installed, operated, maintained and operationally tested in accordance with these instructions at the time of