Installation manual

Remote SAFEPATH Manual Sheet 37 of 50
Rev. C December 1998
Procedure W
If the green NORMAL indicator is off, the yellow TROUBLE indicator is on, and SADC D10 is on, the wiring between the DV channel
play contacts and the backplane is defective or the 10K ohm resistor attached to the DV channel play contacts is defective or
missing.
Perform the following:
1. Verify field wiring between the backplane and the DV is intact.
2. Verify the 10K ohm resistor across the DV channel play contacts is intact. Refer to procedures C, D and E.
Procedure X
If the green NORMAL indicator is off, the yellow TROUBLE indicator is on, and SADC D11 is on, the Battery Charger is defective or
mis-wired
Perform the following:
1. Check the wiring between the backplane and the Battery Charger board.
2. Refer to procedures C, D and E.
Procedure Y
If the green NORMAL indicator is off, the yellow TROUBLE indicator is on, and SADC D12 is on, the Remote Microphone (RMS-1)
has 1 or more troubles.
Perform the following:
1. Verify that field wiring between the backplane and Remote Microphone Station is intact.
2. Verify that all fuses on the SADC are intact.