Instruction manual
P84905-001 G
Sheet 7 of 37
1/2” and 3/4" Knockouts (13)
Figure 2 shows the location of the PC boards and knockouts on the PS-6 panel.
IN1 IN2
CC1
CC2
SBUS
IN
SBUS
RET
SIL
IN
RET1
RET2
COM NONC
TROUBLE
AUX
OUT
NAC1
OUT
NAC2
OUT
NAC3
OUT
TB1
TB2
TB2
TB1
J2
SW1
D2
D9
D37
D3D4
D5D6D7D8
D36 D35 D34
D21
D24
SW5
SW2
SW1
SW3
SW4
SW6
IN1 FOLLOWER
IN2 FOLLOWER
TROUBLE LATCH
SBUS IN1/IN2
GF DET ECT
SBUS SYNC/ TEMPORAL
SYNC PROTOCOL
SYNC P ROTOCO L
NAC1-NAC2 CLASS B/A
NAC3-NAC4 CLASS B/A
AUX POWER CP/MP
SBUS MAST ER/REMOTE
NAC1 SYNC/TEMPORAL
NAC2 SYNC/TEMPORAL
NAC3 SYNC/TEMPORAL
NAC4 SYNC/TEMPORAL
NAC1 IN1/IN2
NAC2 IN1/IN2
NAC3 IN1/IN2
NAC4 IN1/IN2
Figure 2: PS-6 Enclosure Layout
2.0 INSTALLATION INSTRUCTIONS:
NOTE: The POWERPATH NAC Extender Power Supply shall be installed in accordance with the National Fire
Protection Association (NFPA), National Electrical Code (NEC) and all applicable state and local regulations.
2.1 UNPACKING
The POWERPATH was carefully checked before leaving the factory. Inspect shipping container and unit
carefully for indications of improper handling. If damage is detected, make an immediate claim to the carrier.
Remove the POWERPATH from the shipping container and check that the door lock keys, door lock, and
battery connection wires are inside. Make sure the printed circuit boards are within their proper packaging of
the enclosure.
2.2 MOUNTING
TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK, DO NOT EXPOSE THIS UNIT
TO RAIN OR MOISTURE.
This product is not intended for use in hazardous locations as defined by the National
Electrical Code (NEC) and by the National Fire Protection Association (NFPA).
A Mount the POWERPATH in the desired location using the mounting dimensions in Figure 3 (PS-8) and
Figure 4 (PS-6).
B. Mount the panel in an indoor and dry area that does not exceed a temperature range of 32 F to 120 F (0
C to 49 C) and a humidity equal to 10% to 85% at 86 F (30 C) non-condensing.
NOTE: When mounting on interior walls, use proper screw anchors in plaster. When mounting to concrete,
especially when moisture is expected, first attach a piece of ¾ inch plywood to the concrete surface.
Attach the POWERPATH to the plywood.
C. Remove desired knockouts and mount conduit and conduit fittings to the enclosure.
Battery Compartment for
two – 12V, 7Ahrs
Rechargeable Batteries
Power Supply/Battery
Charger PC Board
Control PC Board