Instruction manual
P84905-001 G
Sheet 31 of 37
Example 14: NON-RESETTABLE POWER APPLICATION
IN1
IN2
CC1
CC2
SBUS
IN
SBUS
RET
SIL
IN
RET1
RET2
COM
NC
NO
TROUBLE
AUX
OUT
NAC1
OUT
NAC2
OUT
NAC3
OUT
NAC4
OUT
TB1
TB2
TB1
NO
COM
NC
SW6
SW2
SW1
SW4
SW3
X
If door holder does not include an integrated diode one must be added to each door holder as shown in Example 14.
Ensure that JP1 is installed on the Power Supply PCB (The top pc board.)
The maximum current rating for a NAC OUT circuit is 3.0 Amps.
The maximum current rating for all NAC OUTS must not exceed 4.0 Amps.
For a List of Compatible Auxiliary Devices see table in Section 8.0 on sheet 33.
NOTE: Continuous duty power supply outputs ARE NOT battery backed up. These outputs will TURN OFF if AC Mains
power is lost. These outputs will AUTOMATICALLY TURN ON when AC Mains power is restored.
WARNING: OUTPUTS CONFIGURED AS “CONTINUOUS DUTY POWER SUPPLY OUTPUTS” WILL NOT
SYNCHRONIZE STROBES.