Instruction manual
P84905-001 G
Sheet 25 of 37
Example 5: WHEELOCK SYNC MODE without Audible Silence (CLASS A)
JUMPER WIRE
FOR UNUSED OUTPUT
FACP
NAC
CIRCUIT
10K OHMS
EOLR
OR EOLR (10K OHMS)
TO NEXT APPLIANCE
FACP
NAC
CIRCUIT
RETURN
EOLR COMPATIBLE
WITH FACP
TO FACP
SUPERVISORY
NAC
IN1
IN2
CC1
CC2
SBUS
IN
SBUS
RET
SIL
IN
RET1
RET2
COM
NO
NC
TROUBLE
AUX
OUT
NAC1
OUT
NAC2
OUT
NAC3
OUT
NAC4
OUT
TB1
TB2
TB6
TB3
TB4
SW2
SW1
SW3
SW4
IN2 FOLLOWER OFF/ON
TROUBLE LATCH OFF/ON
SBUS IN1/I N2
GF DETECT ON/OFF
SBUS SYNC/TEMPORAL
SYNC PROTOCOL
SYNC PROTOCOL
NAC1-NAC2 CLASS A/B
NAC3-NAC4 CLASS A/B
AUX POWER CP/MP
SBUS MASTER/REMOTE
NAC4 SYNC/TEMPORAL
NAC4 IN1/IN2
NAC3 IN1/IN2
NAC2 IN1/IN2
NAC1 IN1/IN2
IN1 FOLLOWER OFF/ON
SW6
NAC3 SYNC/TEMPORAL
NAC2 SYNC/TEMPORAL
NAC1 SYNC/TEMPORAL
D30
IN2
D31
D36
INPUT1
INPUT2
D38
SILENCE
D2
GENERAL TROUBLE
D37
ACTIVE
SW5
D40
D3: GROUND FAULT TROUBLE
D4-D8: SEE
TABLE 9
< D8-D4 >
SYNC BUS
GROUND FAULT
LOCATOR
D9
POWER
D1
IN1 TROUBLE
X
Note: To monitor trouble in Class A Mode, only use the “COM”, “NC” and “NO” terminals.
Example 6: TEMPORAL MODE (CLASS A)
JUMPER WIRE
FOR UNUSED OUTPUT
FACP
NAC
CIRCUIT
10K OHMS
EOLR
OR EOLR (10K OHMS)
TO NEXT APPLIANCE
FACP
NAC
CIRCUIT
RETURN
EOLR COMPATIBLE
WITH FACP
TO FACP
SUPERVISORY
NAC
IN1
IN2
CC1
CC2
SBUS
IN
SBUS
RET
SIL
IN
RET1
RET2
COM
NO
NC
TROUBLE
AUX
OUT
NAC1
OUT
NAC2
OUT
NAC3
OUT
NAC4
OUT
TB1
TB2
TB6
TB3
TB4
SW2
SW1
SW3
SW4
IN2 FOLLOWER OFF/ON
TROUBLE LATCH OFF/ON
SBUS IN1/IN2
GF DETECT ON/OFF
SBUS SYNC/TEMPORAL
SYNC PROTOCOL
SYNC PROTOCOL
NAC1-NAC2 CLASS A/B
NAC3-NAC4 CLASS A/B
AUX POWER CP/MP
SBUS MASTER/REMOTE
NAC4 SYNC/TEMPORAL
NAC4 IN1/IN2
NAC3 IN1/IN2
NAC2 IN1/IN2
NAC1 IN1/IN2
IN1 FOLLOWER OFF/ON
SW6
NAC3 SYNC/TEMPORAL
NAC2 SYNC/TEMPORAL
NAC1 SYNC/TEMPORAL
D30
IN2
D31
D36
INPUT1
INPUT2
D38
SILENCE
D2
GENERAL TROUBLE
D37
ACTIVE
SW5
D40
D3: GROUND FAULT TROUBLE
D4-D8: SEE
TAB L E 9
< D8-D4 >
SYNC BUS
GROUND FAULT
LOCATOR
D9
POWER
D1
IN1 TROUBLE
X
CAUTION: Strobes require constant voltage and will not operate properly in the TEMPORAL MODE. A second output
set in the NORMAL MODE will provide the constant voltage.
CAUTION: Only use audible appliances that can use a coded signal. Do not use with Wheelock Series AS/AH, NS/NH
or HS4/HS appliances.
Note: To monitor trouble in Class A Mode, only use the “COM”, “NC” and “NO” terminals.