3.0 SETTING THE DIP SWITCHES
3.1 CONTROL PC BOARD
Refer to Figure 9 for the location and setting of the DIP switches on the Control PC board.
1. Set NAC output DIP Switch(s) on SW1 to follow corresponding input (IN1, IN2).
2. See Figure 8 for DIP switch locations and Table 3 for DIP Switch Selection and DIP Switch Settings
SW5
SW2
SW1
SW3
SW4
IN2 FOLLOWER OFF/ON
TROUBLE LATCH OFF/ON
SBUS IN1/IN2
GF DETECT ON/OFF
SBUS SYNC/TEMPORAL
SYNC PROTOCOL
SYNC PROTOCOL
NAC1-NAC2 CLASS A/B
NAC3-NAC4 CLASS A/B
AUX POWER CP/MP
SBUS MASTER/REMOTE
NAC4 SYNC/TEMPORAL
NAC4 IN1/IN2
NAC3 IN1/IN2
NAC2 IN1/IN2
NAC1 IN1/IN2
IN1 FOLLOWER OFF/ON
SW6
NAC3 SYNC/TEMPORAL
NAC2 SYNC/TEMPORAL
NAC1 SYNC/TEMPORAL
GROUND FAULT TEST
LOCATOR SWITCH
Figure 9: Control PC Board DIP Switches
Table 3: Control PC Board DIP Switch Settings
DIP
Switch
Function
Description
Dip Switch Setting:
“LEFT”
Dip Switch Setting:
“RIGHT”
Dip Switch Setting:
“LEFT”
Dip Switch Setting:
“RIGHT”
SW6
Position 1
TROUBLE
LATCH
OFF / ON
Any trouble conditions will
clear automatically as the
trouble condition is
repaired.
Trouble indicators latch ON
until this switch is switched
to the disable (LEFT)
position or all power is
removed from the panel.
Same Functionality as
Master Mode.
Same Functionality as
Master Mode.
Position 2
SBUS
IN1 / IN2
If IN1 Follower = ON, SBUS
will repeat the signals on
IN1 / CC1 input.
If IN2 Follower = ON,
SBUS will repeat the
signals on IN2 / CC2 input.
If IN1 Follower = ON, NAC
Output(s) set to trigger on
IN1 / CC1 will repeat the
signals on the SBUS when
IN1 / CC1 “Activates.”
If IN1 Follower = ON, NAC
Output(s) set to trigger on
IN1 / CC1 will repeat the
signals on IN1 / CC1 input,
ignoring the NAC Output’s
SYNC / TEMPORAL
dipswitch settings.
If IN1 Follower = OFF,
SBUS will generate signals
according to its SW2 -
SYNC / TEMPORAL switch
setting.
If IN2 Follower = OFF,
SBUS will generate signals
according to its SW2 - SYNC
/ TEMPORAL switch setting.
If IN1 Follower = OFF, NAC
Output(s) set to trigger on
IN1 / CC1 will repeat the
signals on the SBUS when
IN1 / CC1 “Activates.”
If IN1 Follower = OFF, NAC
Output(s) set to trigger on
IN1 / CC1 will repeat the
signals on the SBUS when
IN1 / CC1 “Activates.”
Position 3
IN2
FOLLOWER
OFF / ON
NAC Output(s) or SBUS set
to trigger on IN2 / CC2 will
generate signals according
to its SYNC / TEMPORAL
switch setting.
NAC Output(s) or SBUS set
to trigger on IN2 / CC2 turn
on when IN2 / CC2 is
“Active” and will apply NAC
reverse supervision voltage
when IN2 / CC2 is “Not
Active.”
See SW6 Position 2’s
description for this setting.
See SW6 Position 2’s
description for this setting.