FireForce 8 Installation & Operation Manual P/N 52257:B 09/27/2006 17
Section 4: Operation
4.1 Start-up Procedure
Connect A.C. first, then connect batteries
4.2 Operating Instructions
4.2.1 Alarm Condition
Alarm devices operate in unison with the Main FACP alarm devices. The alarm-activated outputs
are reset through operation of the Reset switch on the Main FACP.
4.2.2 Trouble Condition
The associated trouble LED (yellow) will illuminate.
4.2.3 Testing and Maintenance
System Testing should be performed periodically to insure proper operation.
1. Test the indicating circuits by initiating an alarm or test at the Main FACP.
2. Test for proper operation by actuating the notification appliance circuit the FIREFORCE 8 is
monitoring.
3. Standby batteries and AC transfer are tested by interrupting the AC power line while an alarm
test condition exists (see 1 above).
4.3 Battery Applications
4.3.1 Battery Capacity
Battery Capacity is 26 ampere-hours maximum for the FIREFORCE 8 using the internal battery
charger. The max. charging rate is 0.75 amps. Larger capacity batteries can be used with the
FireForce 8 if they are housed in an external UL listed enclosure, and use an external UL listed
battery charger with sufficient capacity to restore the full charge to the batteries in the required
time. To use an external battery charger, remove the jumper at J1. The alternate enclosure and
battery charger shall be Listed for Fire Protective Signaling use.