Instruction manual

P82475 K
Sheet 4 of 9
Table 5A: Vertical Plane
Vertical 15cd 15cd* 30cd 75cd
Angle (in deg.) UL Min.** Typ. LS Typ. LSM UL Min.** Typ. MS UL Min.** Typ. IS
0 15.0 21 100 30.0 42 75.0 90
5 13.5 21 100 27.0 42 67.5 88
10 13.5 21 100 27.0 42 67.5 87
15 13.5 20 100 27.0 40 67.5 83
20 13.5 19 100 27.0 38 67.5 79
25 13.5 19 98 27.0 38 67.5 74
30 13.5/11.3 18 96 27.0/22.5 36 67.5/56.3 70
35 9.8/11.3 18 94 19.5/22.5 36 48.8/56.3 68
40 6.9/11.3 16 92 13.8/22.5 32 34.3/56.3 66
45 5.1/11.3 14 90 10.2/22.5 28 25.5/56.3 63
50 4.0/8.3 12 84 8.1/16.5 24 20.0/41.3 59
55 3.3/6.8 12 77 6.6/13.5 24 16.3/33.8 54
60 2.7/6.0 9 70 5.4/12.0 18 13.5/30.0 52
65 2.4/5.3 8 63 4.8/10.5 16 12.0/26.3 40
70 2.3/5.3 8 56 4.5/10.5 16 11.3/26.3 31
75 2.0/4.5 8 50 4.0/9.0 16 10.0/22.5 29
80 1.8/4.5 8 30 3.6/9.0 16 9.0/22.5 29
85 1.8/3.8 8 20 3.6/7.5 16 9.0/18.8 28
90 1.8/3.8 8 8 3.6/7.5 16 9.0/18.8 24
*15cd models are Listed at 15cd and meet 75cd on axis.
** Wall/Ceiling
Table 6: Typical Flashes Per Second Across Rated Voltage Range
Models Volts 20.0 22.0 24.0 26.0 28.0 31.0 10.5 12.0 15.6
LS DC 1.0 1.1 1.3 1.4 1.5 1.7 0.9 1.0 1.5
FWR 1.0 1.1 1.3 1.4 1.6 1.8 0.9 1.0 1.5
LSM DC 1.0 1.2 1.3 1.4 1.5 1.6 0.9 1.0 1.6
FWR 1.0 1.2 1.3 1.4 1.5 1.7 0.9 1.0 1.5
MS DC 1.0 1.1 1.2 1.4 1.5 1.6 0.9 1.0 1.6
FWR 1.0 1.1 1.2 1.4 1.4 1.6 0.9 1.0 1.4
IS DC 1.1 1.2 1.3 1.3 1.4 1.5 ------ ------ ------
FWR 1.0 1.1 1.2 1.3 1.3 1.4 ------ ------ ------
NOTE: ADA guidelines presently specify a flash rate of 1 to 3 flashes per second.
MULTITONE SETTINGS: (The Jumper Plug DP1 is used to set dBA sound pressure level for 12VDC versions only.)
The Jumper Plug (DP1) and Switch (SW1) of the Multitone Strobe Appliances, shown in Figure 1, are used to set the dBA sound
output level and alarm tone. The factory settings are shown below. Read these instructions carefully before changing any of these
factory settings.
Figure 1.
PC Board Layout Showing Location
of Jumper Plug (DP1) and Switch (SW1)
1
2
3
4
SW1
4
3
2
1
SW1
+ STB -
+ AUD -
SLIDE HERE FOR (0)
SLIDE HERE FOR (1)
ON
ON
The factory settings for 12VDC models are:
12VDC DP1 set on 12VDC
HIGH dBA: SW1 POS 1 set on 1
HORN TONE: SW1 POS 2, 3, 4 set on 1, 1, 1
The factory settings for 24VDC models are:
HIGH dBA: SW1 POS 1 set on 1
HORN TONE: SW1 POS 2, 3, 4 set on 1, 1, 1