Instruction manual

3.2 PS2/3/5 Board Terminal Descriptions and Electrical Ratings
Low-Current Fault Output -FAULT OUTPUT -
For connection to AlarmSaf RBKS module ONLY - See
Section 3.6 and Appendix A
Low-Current Fault Output +FAULT OUTPUT +
Units with Voltage Fault Output
Fault Relay Output Normally OpenFAULT OUTPUT NO
Fault Relay Output CommonFAULT OUTPUT C
1 Amp at 24VDC (Resistive) - Contacts are labeled in
the non-powered (Fault) condition
Fault Relay Output Normally ClosedFAULT OUTPUT NC
Units with Relay Fault Output
DC Common OutputDC OUTPUT -
12VDC or 24VDC at full output current of supply - See
Table 3.1 for ratings.
DC Positive OutputDC OUTPUT +
TB2 - DC Output and Fault Output
Negative Battery ConnectionBATTERY CONNECT -
12VDC or 24VDC at 14AH - 38AH - See Table 3.1 for
Ratings
Positive Battery ConnectionBATTERY CONNECT +
LOW VOLT AC
CONNECT
17.5VAC or 28.2VAC - See Table 3.1 for RatingsLow voltage AC input
LOW VOLT AC
CONNECT
TB1 - Low Voltage AC Input and Battery Output
RatingDescriptionTerminal / Connector
Figure 3.2
AC FUSE
BAT
FUSE
LVAC
CONNECT
BAT
CONNECT
DC
OUTPUT
FAULT
OUTPUT
W5
D12
R21
R7
F2
F1
TB2
TB1
A1
S1
R16
AC FLT
DC FLT
24/12V
AC
CONNECT
BATTERY
CONNECT
VOLTAGE AC
LOW
REF
ADJREG
ADJ
BFF
ADJ
DC
OUTPUT
FAULT
OUTPUT
PS2
PS3
PS5
PS5-UL
AlarmSaf
1
2
3
4
1, 2 OPEN = 24V
3 OPEN = DC FLT DISABLE
4 OPEN = AC FLT DISABLE
AC
FUSE
BAT
FUSE
FUSE RATINGS
AGC-10
+
-
+
-
+
-
FLT
RED LED
A VISUAL INDICATOR
NOT
Note: Wire should be sized appropriately for voltage drop and current carrying capability. All
terminals are labeled for polarity where appropriate.
PS2/3/5 Installation Instructions
8/23/2007, 2:51:41 PM
52-133 Rev B.01
Page 7 of 16
AlarmSaf 65A Industrial Way, Wilmington, MA 01887 978 658 6717 www.alarmsaf.com