Instruction manual
Section 5
Operating the PS2/3/5
5.1 Setting the DIP Switches (Non-Listed supplies only)
Before powering a system containing a PS2/3/5, the DIP Switches should be set for proper operation.
The PS2/3/5 board may have either 4 switches or 8 switches, depending on the age of the supply.
Note - Due to inconsistencies by the manufacturers of DIP switches in the labeling of switch numbers
and ON and OFF positions, AlarmSaf indicates switch settings visually and descriptively.
Note - All switch settings shown below are indicated with the board positioned so that the terminal
strips are to the right and the large heatsink is to the left as seen in Figure 5.1.
5.1.1 Supplies with Four Switches
Right (On / Closed)N/AN/AN/ABottom Switch
N/ARight (On / Closed)N/AN/A
Third Switch
N/AN/ALeft (Off / Open)Right (On / Closed)
Second Switch
N/AN/ALeft (Off / Open)Right (On / Closed)
Top Switch
AC Faults EnableDC Faults Enable24V Output12V Output
5.1.2 Supplies with Eight Switches
N/ALeft (On / Closed)N/AN/ABottom Switch
Left (On / Closed)N/AN/AN/A
Seventh Switch
N/AN/ARight (Off / Open)Left (On / Closed)
Sixth Switch
N/AN/ARight (Off / Open)Left (On / Closed)
Fifth Switch
N/AN/ARight (Off / Open)Right (Off / Open)
Fourth Switch
N/AN/ARight (Off / Open)Left (On / Closed)
Third Switch
N/AN/ARight (Off / Open)Left (On / Closed)
Second Switch
N/AN/ARight (Off / Open)Right (Off / Open)
Top Switch
AC Faults EnableDC Faults Enable24V Output12V Output
W5
R21
F1
TB2
TB1
S1
AC FLT
DC FLT
24/12V
AC
CONNECT
BATTERY
CONNECT
VOLTAGE AC
LOW
DC
OUTPUT
FAULT
OUTPUT
AlarmSaf
1
2
3
4
1, 2 OPEN = 24V
3 OPEN = DC FLT DISABLE
4 OPEN = AC FLT DISABLE
AC
FUSE
BAT
FUSE
+
-
+
-
+
-
FLT
W5
R21
F1
TB2
TB1
S1
AC FLT
DC FLT
AC
CONNECT
BATTERY
CONNECT
VOLTAGE AC
LOW
DC
OUTPUT
FAULT
OUTPUT
AlarmSaf
AC
FUSE
BAT
FUSE
+
-
+
-
+
-
FLT
1
8
Figure 5.1
PS2/3/5 Installation Instructions
8/23/2007, 2:51:41 PM
52-133 Rev B.01
Page 12 of 16
AlarmSaf 65A Industrial Way, Wilmington, MA 01887 978 658 6717 www.alarmsaf.com