Specifications

Model SK-2224 Fire Control Panel Installation/Operation Manual
4-10 151051
Setting the SK-2865’s address
The range of valid addresses is 0-3. Each device requires a unique address. Set the dip
switches as shown in Table 4-3. See also Figure 4-9.
Mounting the SK-2865
The SK-2865 mounts into a standard 4” square electrical box.
Follow these steps to mount the SK-2865:
1. Make sure that the SK-2865 is properly wired to the control panel. See Figure 4-9.
2. Slide the printed annunciator label into place on the SK-2865. The label fits in between the
LEDs and the clear plastic plate.
3. Place the SK-2865 into the 4” square electrical box. See Figure 4-10.
Figure 4-10 Mounting the SK-2865
4. Place the cover plate over the top of the SK-2865 and align the holes. See Figure 4-10.
5. Insert the four cover plate screws into the four screw holes on the 4” square electrical box.
6. Screw the four cover plate screws into the cover plate until the cover plate fits firmly
against the SK-2865 and the electrical box. Do not over tighten.
Table 4-3: Addresses Per Dip Switch Setting
Dip Switch Position
Equivalent
Address
Both Open (off) 0
One Closed (on) 1
Two Closed (on) 2
Both Closed (on) 3
Cover Plate
Screw
Cover Plate
Annunciator
Label In
Slide Printed
4” Square
Electrical Box
SK-2865