Content Section 1 Overview 1.1 1.2 ...................................................................................................................................................... 1-1 SK-2224 Description ................................................................................................................................ 1-1 How to Contact Silent Knight ..................................................................................................................
Model SK-2224 Fire Control Panel Installation/Operation Manual 4.7 Optional Accessories Installation ............................................................................................................. 4-7 4.7.1 Installing the Serial Driver Board (Model SK-2884) .................................................................... 4-7 Wiring the SK-2884 to an Expansion Device ............................................................................... 4-8 4.7.
Section 1 Overview 1.1 SK-2224 Description The Model SK-2224 is a two zone, 24-volt fire control panel having the following features: • Two Class B zones • Two notification circuits rated at 1.25 amp each • 2.5 amp power supply • Dedicated alarm and trouble relays • Auxiliary power output (.5 amp max.) for powering special applications, such as door holders. • Enhanced Verification Mode, a built-in feature that distinguishes two-wire smoke detectors from pull stations.
Model SK-2224 Fire Control Panel Installation/Operation Manual 1-2 151051
Section 2 Agency Requirements 2.1 FCC Warning This device has been verified to comply with FCC Rules Part 15. Operation is subject to the two following conditions: (1) This device may not cause radio interference, and (2) This device must accept any interference received, including interference that may cause undesired operation. 2.2 Underwriters Laboratories (UL) The SK-2224 is UL listed as a control unit for use in NFPA 72 systems.
Model SK-2224 Fire Control Panel Installation/Operation Manual 2-2 151051
Section 3 Before You Begin Installing 3.
Model SK-2224 Fire Control Panel Installation/Operation Manual 3.2 Optional Accessories Table 3-2 is a list of optional accessories that can be used with the Model SK-2224 Fire Control Panel. Table 3-2: Option Accessories for the SK-2224 Model Number * 3-2 Name Description SK-2884 Serial Driver Board Used to interface all SK-2224 expansion device to the SK2224 panel. Supports 1 Dialer (Model SK-2104) and any combination of 4 LED Annunciators (Model SK-2865) or I/O Modules (Model SK-2880).
Before You Begin Installing 3.3 SK-2224 Board Layout Figure 3-1 shows the SK-2224 circuit board including location of terminals, connectors, dip switches, and LEDs.
Model SK-2224 Fire Control Panel Installation/Operation Manual 3.4 Electrical Specifications Table 3-3: Electrical Specifications Circuit Rating Primary AC *120 Vrms at 60 Hz, or 230 Vrms at 50 Hz Total External DC Load 2.5A @ 24 VDC +24V Auxiliary Power 19.8 V to 28.0 V, 0.5 A max. Trouble & Alarm Relays 2.5 A @ 30 VDC resistive Notification Appliance Power 19.8 V to 28.0 V, 1.25 A max. each Smoke Detector Power 19.8 V to 28.0 V, 1.0 A max. Battery Charging Voltage 27.0 - 27.
Before You Begin Installing 3.6 Mounting the SK-2224 Read the environmental specifications in Section 3.5 before mounting the cabinet. The panel should be accessible to main drop wiring runs. It should be mounted as close to the center of the building as possible and located within a secured area, but should be accessible for testing and service. End-users responsible for maintaining the panel should be able to hear alarms and troubles.
Model SK-2224 Fire Control Panel Installation/Operation Manual 3.7 Assembly The components listed in Table 3-1 are all packed within the cabinet and require some assembly. Follow these steps to assemble the components inside the cabinet: 1. Remove keys from small manila envelope taped to the top of the cabinet. 2. Unlock the cabinet door. 3. Remove the packing material and the SK-2224 components. 4. Snap the bezel into the opening in the front of the cabinet. See Figure 3-3.
Before You Begin Installing 3.8 Wiring Specifications Induced noise (transfer of electrical energy from one wire to another) can cause false alarms or interfere with control panel operation in other ways. To avoid induced noise, follow these guidelines: • Isolate input wiring from high current output and power wiring. Do not pull one multiconductor cable for the entire panel.
Model SK-2224 Fire Control Panel Installation/Operation Manual 3.9 Calculating Current Draw and Standby Battery This section is for helping you determine the current draw and standby battery needs for your installation. 3.9.1 Worksheet Requirements The following steps must be taken when determining SK-2224 current draw and standby battery requirements. Filling in the Current Draw Worksheet, Table 3-6 (Section 3.9.3) 1.
Before You Begin Installing 3.9.3 Current Draw Worksheet Use this worksheet to determine current requirements during alarm/battery standby operation. (Copy this page if additional space is required.
Model SK-2224 Fire Control Panel Installation/Operation Manual 3-10 151051
Section 4 Hardware Installation 4.1 AC Power At installation, connect the transformer AC inputs to the AC power source as shown in Figure 4-1. It may be necessary for a professional electrician to make this connection. The AC inputs are rated as 120 VAC, 60 Hz or 230 VAC, 50 Hz. See Table 3-1 for more information.
Model SK-2224 Fire Control Panel Installation/Operation Manual 4.2 Battery Connection The SK-2224 battery charge capacity is 7.0 AH. Use two 12V batteries of the same AH rating. Determine the correct AH rating as per your current load calculation (see Table 3-6). Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase the AH rating. Note: The SK-2224 cabinet supports two 7.0 AH batteries. Battery jumper (P/N 140694), shipped with the control panel.
Hardware Installation 4.3 4.3.1 Initiation Circuit Installation Contact Wiring Wire normally open contacts as shown in Figure 4-3. This is the type of wiring that would typically be used for water flow switches, heat detectors and other normally open devices. Figure 4-3 N.O. Contact Wiring 4.3.2 Two-Wire Smoke Detector Wiring Figure 4-4 shows how to connect two-wire smoke detectors to the SK-2224 loops. The figure uses Silent Knight's SLK-24F with HSB-224 base as an example.
Model SK-2224 Fire Control Panel Installation/Operation Manual 4.3.3 Four-Wire Smoke Detector Figure 4-5 shows how to connect four-wire smoke detectors to the SK-2224 loops. The figure uses Silent Knight's SLK-24F with HSC-4R base as an example. You can use any UL listed device listed in Appendix A. Information on selecting zone configuration options is in Section 5.
Hardware Installation 4.3.4 Notification Circuit Installation Notification appliances used with the SK-2224 must be UL listed for compatibility with the SK-2224. Refer to the list in the Appendix at the end of this manual for a list of compatible devices. For proper operation, you must use polarized notification appliances with a model 7628 4.7k ohm end-of-line (EOL) resistor on each loop. Select ANSI output pattern, if desired. Output is configured as steady (continuous sound) for the factory default.
Model SK-2224 Fire Control Panel Installation/Operation Manual 4.6 Door Release Wiring Figure 4-7 shows how to configure a door release using an ESL DH series door holder.
Hardware Installation 4.7 Optional Accessories Installation This section describes how to install the optional accessories compatible with the SK-2224 control panel. 4.7.1 Installing the Serial Driver Board (Model SK-2884) The SK-2884 is required if the installation uses any SK-2224 expansion devices such as Model SK2865 (LED Annunciator). The SK-2884 interfaces all the expansion devices to the SK-2224 control panel. Follow these steps to install the SK-2884 Serial Driver Board: 1.
Model SK-2224 Fire Control Panel Installation/Operation Manual Wiring the SK-2884 to an Expansion Device The SK-2884 uses a three wire connection to all of the SK-2224 compatible expansion devices (see Table 3-2). Connect all the expansion devices to the SK-2884 as follows: Table 4-1: SK-2884 Wiring Connections 4.7.
Hardware Installation 3. Terminate the wiring as shown in Figure 4-9. See also Table 4-2.
Model SK-2224 Fire Control Panel Installation/Operation Manual Setting the SK-2865’s address The range of valid addresses is 0-3. Each device requires a unique address. Set the dip switches as shown in Table 4-3. See also Figure 4-9. Table 4-3: Addresses Per Dip Switch Setting Dip Switch Position Equivalent Address Both Open (off) 0 One Closed (on) 1 Two Closed (on) 2 Both Closed (on) 3 Mounting the SK-2865 The SK-2865 mounts into a standard 4” square electrical box.
Hardware Installation 151051 4-11
Model SK-2224 Fire Control Panel Installation/Operation Manual 4-12 151051
Section 5 System Configuration To configure the SK-2224 system set the dipswitch that controls the option you want to select. The following chart shows how to program the dipswitches that control system, zone, and notification appliance operation. Refer to Figure 3-1 for location of the dipswitches. Important! When you change a dipswitch, be sure to perform a system reset (press [RESET]) or power down the panel. Dipswitch changes will have no effect until after the system has been reset.
Model SK-2224 Fire Control Panel Installation/Operation Manual Table 5-1: System Configuration To Enable For Entire Panel (DIP 2) SW5 Serial Accessory Devices *SW6 DIP Position ON = Serial Annunciator connected to the control panel. OFF = No Serial Annunciator connected to the control panel. ON = Serial Dialer connected to the control panel OFF = No Serial Dialer connected to the control panel. ON = 6 hour delay on AC loss report. OFF = No delay on AC (for dialer testing only).
Section 6 System Operation The annunciator on the SK-2224 board is used for all system operation. It contains the switches for enabling silencing, resetting, and so on. The LEDs that indicate system status are also located on the annunciator. Figure 6-1 On-Board Annunciator 6.1 Meaning of LEDs The chart below explains the meaning of LEDs on the system board.
Model SK-2224 Fire Control Panel Installation/Operation Manual Table 6-1: Meaning of LEDs LED (Color) GND FAULT (yellow) Function ON = Ground fault condition exists and was acknowledged Comments If flashing, press the ACK button to acknowledged the condition. OFF = No fault FLASHING = A ground fault condition detected LOW BATTERY (yellow) ON = Battery low condition that has been acknowledged If flashing, press the ACK button to acknowledged the condition.
System Operation 6.2 Operation Keys (Switches) All system operations are performed from the on-board keys (switches) as described in the chart below. Table 6-2: Operations and Instructions Operation Disable notification appliance circuit. To re-enable the circuit, press [NAC DISABLE] again. Disable a zone Keystrokes Press the appropriate [NAC DISABLE] key. The NAC circuit will be disabled and the corresponding TROUBLE LED will Double Flash. This function is not available during an alarm condition.
Model SK-2224 Fire Control Panel Installation/Operation Manual 6-4 151051
Appendix A Compatible Devices This section of the manual lists devices (smoke detectors and notification appliances) that are compatible with the SK-2224. Contact Silent Knight if you have a question about whether a device not listed here is compatible. A.1 Smoke Detectors This section of the manual contains information about smoke detectors that are compatible with the SK-2224. SK-2224 Identifier Voltage Range 24F 16.2 - 27.
Model SK-2224 Fire Control Panel Installation/Operation Manual A.1.2 Two-Wire Smoke Detectors The table below lists two-wire smoke detectors that are compatible with the SK-2224. The table is organized by manufacturer. The columns show the number of detectors per loop that can be used. Note: The check mark by manufacturers name indicates that this device can be used in enhanced mode.
Table A-1: Compatible Two-Wire Smoke Detectors Manufacturer Enhance Mode Compatible Compatibility ID Model Name or Number (Base model name or number in parentheses.
Model SK-2224 Fire Control Panel Installation/Operation Manual A.1.
A.2 Notification Appliances The chart below lists notification appliances compatible with the SK-2224.
Model SK-2224 Fire Control Panel Installation/Operation Manual Table A-3: Compatible Notification Devices Manufacturer A-6 Model Type Faraday 5508B-( )-14-24-DC Single Gang Sync Strobe (flush) Faraday 5521B-( )-14-24-DC 4” Square Sync Strobe (surface) Faraday 5522B-( )-14-24-DC 4” Square Sync Strobe (flush) Faraday 6126B-U-14-24 VDC Horn/Strobe Faraday 6223B-0-14-24-DC Horn (flush) Faraday 6224B-0-14-24-DC Horn (surface) Faraday 6225B-0-4-24-DC Horn (ceiling) Faraday 6226B-( )-14-
Table A-3: Compatible Notification Devices Manufacturer Model Type Gentex HG124 Horn Gentex SHG24-1575 Horn/Strobe Gentex SHG24-15 Horn/Strobe Gentex GMH-24-X Horn Gentex GMS-24-X Horn/Strobe Gentex GMS-24-X Horn/Strobe Gentex G0T24 Horn Gentex G0S24-X Horn Gentex WGMS-24-X Horn/Strobe System Sensor MASS241 Horn/Strobe System Sensor MASS24110ADA Horn/Strobe System Sensor MASS2415ADA Horn/Strobe System Sensor MASS2475ADA Horn/Strobe System Sensor SS4110ADA Strobe
Model SK-2224 Fire Control Panel Installation/Operation Manual Table A-3: Compatible Notification Devices Manufacturer A-8 Model Type Wheelock AES-EL1-WS-24-VF-R Multitone Horn Wheelock AES-DL1-WH-24-VF-R Multitone Horn Wheelock AES-EL1-WH-24-VF-R Multitone Horn Wheelock AES-DL1-WM-24-VF-R Multitone Horn Wheelock AES-EL1-WM-24-VF-R Multitone Horn Wheelock AH-24-R Horn Wheelock AH-24WP-R Horn Wheelock AMT-12\24-R Strobe Horn Wheelock AMT-24-LS-VFR Strobe Horn Wheelock AMT-24-
Table A-3: Compatible Notification Devices Manufacturer Model Type Wheelock CH70-241575W-FR Chime Strobe Wheelock CH70-2430W-FR Chime Strobe Wheelock CH70-2475W-FR Chime Strobe Wheelock CH70-24110W-FR Chime Strobe Wheelock CH-CF1 Chime Wheelock CH-CF1-R Chime Wheelock CH-CF1-W Chime Wheelock CH-DF1 Chime Wheelock CH-DF1-R Chime Wheelock CH-BF1-WS-24-HF-R Strobe Chime Wheelock CH-CF1-LS-24 Strobe Chime Wheelock CH-CF1-MS-24 Strobe Chime Wheelock CH-CF1-IS-24 Strobe Ch
Model SK-2224 Fire Control Panel Installation/Operation Manual Table A-3: Compatible Notification Devices Manufacturer A-10 Model Type Wheelock EH-EL1-WS-24-VF-R Strobe Horn (dual input) Wheelock EH-DL1-WH-24-VF-R Strobe Horn (dual input) Wheelock EH-EL1-WH-24-VF-R Strobe Horn (dual input) Wheelock EH-DL1-WM-24-VF-R Strobe Horn (dual input) Wheelock EH-EL1-WM-24-VF-R Strobe Horn (dual input) Wheelock HSW-24-HFR Remote Strobe Wheelock HS2W-24-HFR Remote Strobe Wheelock HSPW-24-HFR
Table A-3: Compatible Notification Devices Manufacturer Model Type Wheelock MIZ-24-MS-VFR Mini-Horn/Strobe Wheelock MIZ-24-HSW-HFR Mini-Horn/Strobe Wheelock MIZ-24-IS-VFR Mini-Horn/Strobe Wheelock MIZ-24-WS-VF-R Mini-Horn/Strobe Wheelock MIZ-24-WS-VF-W Mini-Horn/Strobe Wheelock MIZ-24-WH-VF-W Mini-Horn/Strobe Wheelock MIZ-24-WM-VF-W Mini-Horn/Strobe Wheelock MT-12/24-R Strobe Horn Wheelock MT4-12/24-R Multitone Appliance Wheelock MT4-115-R Multitone Appliance Wheelock MT-24
Model SK-2224 Fire Control Panel Installation/Operation Manual Table A-3: Compatible Notification Devices Manufacturer A-12 Model Type Wheelock RS-241575W-FR Strobe Wheelock RS-2415-HFR Strobe Wheelock RSP-2415-VFR Strobe Wheelock RS-241575-VFR Strobe Wheelock RSP-241575-VFR Strobe Wheelock RS-2430-VFR Strobe Wheelock RS-2430-HFR Strobe Wheelock RS-2475-VFR Strobe Wheelock RSP-2475-HFR Strobe Wheelock RS-24110-HFR Strobe Wheelock RSP-24110-HFR Strobe Wheelock RSS-2415W
Table A-3: Compatible Notification Devices Manufacturer Model Type Wheelock SLPM-24-VFR Synchronized Remote Strobe Wheelock SHW-24-VFR Synchronized Remote Strobe Wheelock SH2W-24-VFR Synchronized Remote Strobe Wheelock SHPW-24-VFR Synchronized Remote Strobe Wheelock SCM-24-R Controller for Synchronized Strobes Wheelock SM-12/24-R Sync Module Wheelock SR-2415-VFR Sync Strobe Wheelock SRP-2415-HFR Sync Strobe Wheelock SR-241575-VFR Sync Strobe Wheelock SRP-241575-VFR Sync Strob
Model SK-2224 Fire Control Panel Installation/Operation Manual A-14 151051
Silent Knight Fire Product Warranty and Return Policy General Terms and Conditions • All new fire products manufactured by Silent Knight after September 1, 1997 have a limited warranty period of 18 months from the date of manufacture against defects in materials and workmanship. See limited warranty statement for details. • This limited warranty does not apply to those products that are damaged due to misuse, abuse, negligence, or have been modified in any manner whatsoever.
Model SK-2224 Fire Control Panel Installation/Operation Manual • A new or refurbished board will be shipped to the customer. The customer will initially be billed for the replacement board but a credit will be issued after the repairable board is received at Silent Knight. • The defective board must be returned within 30 days of shipment of replacement board for customer to receive credit. No credit will be issued if the returned board was damaged due to misuse or abuse.
SK-2224 Basic Operating Instructions P/N 151055 These instructions must be framed and displayed next to the SK-2224 panel in accordance with NFPA 72 fire code for Local Fire Alarm System.