Specifications

Appendix B: Battery Calculations (Selection Guide)
14
Appendix B: Battery Calculations (Selection Guide)
Use the form below to determine the required batteries.
Total Current Requirement
ALARM (B)______ Amps.
Battery Capacity Requirement
(
[STANDBY (A) ______ ] X [(24 or 60 Hours) ________ ]) + ([ALARM (B) ______ ] X [
Alarm in Hr.] ________) = (C) ________AH
Battery Selection
Multiply (C) by 1.20 to derate battery.
* Assuming three Initiating Circuits in alarm.
Use 0.084 for five minutes of alarm or 0.5 for thirty minutes of alarm as a multiplier figure.
Using the MIR-525/U 2-wire smoke detector. See Appendix "A", for other available smoke detectors .
IMPORTANT NOTICE
The main AC branch circuit connection for the Fire Alarm Control Unit must provide a dedicated
continuous power without provision of any disconnect devices. Use #12 AWG wire with 600-volt
insulation and proper over-current circuit protection that complies with the local codes.
Power Requirements (All currents are in amperes)
Model Number Description Qty Standby
Total
Standby
Alarm Total Alarm
PFC-3002T
Fire Alarm, 2 Det, 1
Sig
X 0.076 = 0.135 =
RTI-1
Remote Trouble
Indicator
X 0.035 = 0.035 =
2-Wire Smoke Detectors X
0.0001
= * 0.090 = 0.090
4-Wire Smoke Detectors X = =
Signal Load (bells, horns, strobes, and
etc.)
=
Total currents (Add above currents) Standby (A)(B)
Note: Batteries BT-40 (4.0AH) and BT-80 (8AH) fit into the backboxes; all larger batteries
such as BT-120 (12AH) and the BT-180 (18AH) require an external battery box.