PFC-3002T Installation and Operation Manual Contents List of Figures.......................................................................................................................... Introduction ............................................................................................................................. Mechanical Installation ........................................................................................................... Function Selection ..............................
List of Figures List of Figures Figure 1: Backbox and flush trim mounting details .................................................................... Figure 2: Circuit Board Layout ................................................................................................... Figure 3: Detection and signal wiring......................................................................................... Figure 4: Wiring table for detection zone ............................................................
PFC-3002T Installation and Operation Manual Introduction The PFC-3002T is a supervised two-zone 24VDC Fire Alarm Control Panel. The panel provides the following features: • Two Class B detection zones • One Class B signal zone, 1.7A • DIP switch selectable signal circuit outputs such as temporal or steady • Alarm and trouble relay contacts • Remote trouble and A.C.
Wiring DIP switch DSW1 is used to set the preferred signal zone 1 output, the signal silence inhibit, and the common trouble flash rate. The default output for the signal zone is temporal code. not used ON DIP switch DSW1 1 2 3 4 5 6 7 8 Signal Zone Trouble Buzzer and LED ON - steady OFF - temporal code (default) ON - steady buzzer and LED OFF - Pulsing Buzzer and LED (default) ON - 1 minute signal silence inhibit OFF - normal signal silence (default) • Temporal Code: 3 rounds of 0.
PFC-3002T Installation and Operation Manual Remote Annunciation Annunciation outputs are provided for remote trouble indicator and buzzer. Refer to Figure 6 on page 9 for wiring instruction. A.C. Power and Batteries The A.C. power is connected to the terminal block above the transformer. Use Gel Cell or Sealed Lead-Acid type of batteries only. Connect the batteries after power up. Use 24V 4AH batteries for 24 hours standby and 5 or 30 minutes of alarm.
Sequence of Operation Sequence of Operation Refer to Figure 2 on page 6 for the location of indicators and controls. Normal All indicators are normally OFF except for the green A.C. On LED. Alarm A red zone alarm LED will illuminate steadily for an incoming alarm. Signal Silence If the 60 second signal silence inhibit is selected, the signal cannot be silenced for 60 seconds after an alarm initiation.
Figure 1: Backbox and flush trim mounting details 1 11/ 13 3/4” 10 3/8” 16” 1 1/ 4” Optional flush mounting trim (model FA-102TR) 7 1/ 8” 12 3/4” 7/ 32” dia.
+ - + 1 + - - JW4 SIGNAL DETECTION ZONE 2 1 JW3 COM (-) TB2 6 Figure 2: Circuit Board Layout AUX. ALARM RELAY NO C NC TRBL RELAY REMOTE ANNUNCIATION TRL TRB A.C. ON 24V + BUZZER SIL. JW1 ZONE 1 SIL. A.C. ON JW2 ALARM TRBL. ZONE 1 TRBL. ALARM TRBL. ZONE 2 ZONE 2 SIL. SIG. SIL. BATT. F2 GND 2A A.C. TRANSFORMER P1 SIG.
PFC-3002T Installation and Operation Manual Figure 3: Detection and signal wiring Legend F Pull Station S Smoke Detector Heat R Detector F Bell Alarm threshold current is 21 mA. Maximum loop resistance is 100 ohms. TB2 + 22VDC 3mA STBY 5mV ripple 50 mA max. alarm Detection zone 1 F S R ELR 3.9K 1/2W R ELR 3.9K 1/2W Detection zone 2 22VDC 3mA STBY 5mV ripple 50 mA max. alarm F S + 24VDC unfiltered 1.7A max. Signal zone F F ELR 3.
Wiring Tables and Information Wiring Tables and Information Figure 4: Wiring table for detection zone Wire Gauge Maximum Wiring Run to Last Device (ELR) (AWG) ft. m 22 2990 910 20 4760 1450 18 7560 2300 16 12000 3600 14 19000 5800 12 30400 9200 Note: Maximum loop resistance should not exceed 100 ohms. Figure 5: Wiring table for bells and horns Signal circuit is rated for 1.7 amperes each.
PFC-3002T Installation and Operation Manual Figure 6: Alarm and trouble relay contacts and remote annunciation wiring instructions TS2 N.O. C Auxiliary common alarm relay contacts 28VDC, 3A (resistive) N.C. Common trouble relay contacts 28VDC, 3A (resistive) TRL 1.5K unsupervised 24VDC, 50 mA max. TRB 24VDC, 50 mA max. A.C. ON Cut JW4 for N.C. remote trouble LED (amber) 1.5K unsupervised Cut JW3 for N.O. 1.5K remote trouble buzzer remote AC ON LED (green) 24V+ 24VDC, 250 mA max.
Appendix A: Compatible Devices Appendix A: Compatible Devices Underwriter’s Laboratories Canada (ULC) Canadian 2-Wire Smoke Detector Control Panel Notes: • Reset time, hold for five seconds minimum. • Whether mixing different models of compatible smoke detectors, or using the same model on the same Circuit, total standby current of all detectors must not exceed 3 mA.
PFC-3002T Installation and Operation Manual Underwriter’s Labs Inc. (ULI) United States 2-Wire Smoke Detector Control Panel Compatibility Notes: • Reset time, hold for five seconds minimum. • Whether mixing different models of compatible smoke detectors, or using the same model on the same circuit, total standby current of all detectors must not exceed 3 mA. • The below-listed smoke detectors are compatible with initiating circuits having Compatibility Identifier "A".
Appendix A: Compatible Devices Smoke Detector Make Model / Base Compatibility Identifier Head / Base Rated Standby Current System Sensor (cont’d) Smoke Detector Make Model / Base Compatibility Identifier Head / Base Rated Standby Current Sentrol - ESL (cont’d) 732U / 702E, 702U, 702RE, 702RU 2400 A - N/A 0.12 mA 2400TH A - N/A 0.12 mA 2400AT A - N/A 0.12 mA Detection Systems Inc. 2400AIT A - N/A 0.12 mA DS250 B - N/A 0.10 mA 2451 / B401B A-A 0.12 mA DS250TH B - N/A 0.
PFC-3002T Installation and Operation Manual Underwriter’s Labs Inc.
Appendix B: Battery Calculations (Selection Guide) Appendix B: Battery Calculations (Selection Guide) Use the form below to determine the required batteries. IMPORTANT NOTICE The main AC branch circuit connection for the Fire Alarm Control Unit must provide a dedicated continuous power without provision of any disconnect devices. Use #12 AWG wire with 600-volt insulation and proper over-current circuit protection that complies with the local codes.
PFC-3002T Installation and Operation Manual Warranty Potter Electric Signal Co., manufactured equipment is guaranteed to be free of defects in material and workmanship for a period of one (1) year from the date of original shipment. Potter will repair or replace, at its option, any equipment which it determines to contain defective material or workmanship. Said equipment must be shipped to Potter prepaid. Return freight will be prepaid by Potter.