Installation manual
Installation Manual
150933 / Rev. 9/96 9
Table 4-2. Battery Calculation Worksheet
Device Number
of
Devices
Current per Device Standby
Current
Alarm
Current
For each device use this formula: This column X This column = Current per number of devices.
5395 Distributed Power Module 1 Standby: 75 mA 75 mA
(Current draw from battery) Alarm: 100 mA 100 mA
A
5395 Current
75 mA 100 mA
Auxiliary Devices Refer to device manual for current ratings.
Alarm/Standby mA mA mA
Alarm/Standby mA mA mA
Alarm/Standby mA mA mA
Alarm/Standby mA mA mA
B
Auxiliary Devices Current
mA mA
Notification appliances Refer to device manual for current ratings.
Alarm: mA 0 mA mA
Alarm: mA 0 mA mA
Alarm: mA 0 mA mA
Alarm: mA 0 mA mA
C
Notification Appliances Current
0 mA mA
D Total current ratings of all devices in system (line A + line B + line C) mA mA
E Total current ratings converted to amperes (line D x .001): A A
F Number of standby hours (24 or 60 for NFPA 72, Chapter 1, 1-5.2.5). H
G Multiply lines E and F. Total standby AH AH
H Alarm sounding period in hours.
(For example, 5 minutes = .0833 hours.)
H
I Multiply lines E and H. Total alarm AH AH
J Add lines G and I. Total standby and alarm AH AH
K Multiply line J by 1.20. (20% extra insurance to meet desired performance)
Total ampere-hours required
AH