Installation manual
Installation Manual
150933 / Rev. 9/96 3
3. System Overview
CAUTION
Each output circuit is rated at 3 amps. DO NOT OVERLOAD. Overloading a circuit will cause it to shut
down (power limit). The circuit will automatically reset once you remove the overload condition.
3.1 Terminal Descriptions and Electrical Ratings
Table 3-1. Terminal Descriptions
Terminal # Description Ratings
TB1
1
AC (black“hot”)
120 VAC 60 Hz
2 Earth Ground
3
AC (white“neutral”)
TB2
1 Auxiliary Power (-)
2 Auxiliary Power (+) 24 VDC 3.0 amps
3 Notification 4 Output (-)
4 Notification 4 Output (+) 24 VDC 3.0 amps
Even though each output
5 Notification 3 Output (-)
is rated for 3 amps, the
6 Notification 3 Output (+) 24 VDC 3.0 amps
total current draw from
7 Notification 2 Output (-)
the 4 outputs and the
8 Notification 2 Output (+) 24 VDC 3.0 amps
auxiliary power must
9 Notification 1 Output (-)
not exceed 6 amps of
10 Notification 1 Output (+) 24 VDC 3.0 amps
notification power.
11 Normally Closed contact
2.5 A @ 250 VAC
12 Common
or
13 Normally Open contact
2.5 A @ 30 VDC
14 Input 2
15 Input 2 (-) 9 - 30 VDC
16 Input 2 (+)
17 Input 1
18 Input 1 (-) 9 - 30 VDC
19 Input 1 (+)