Installation manual

Installation Manual
150933 / Rev. 9/96 19
4.7.2 Setting the Loss of AC Delay
Normal selection for reporting loss of AC is 6 hours.
The ON position is for test purposes only and the normal position for switch 4 is OFF. For
testing the Low AC reporting, you can temporarily turn switch 4 ON without removing power.
Remember to turn the switch OFF when testing is complete.
12
3
45
12
3
4
5
OFFON
dips4
Figure 4-8. Setting DIP Switch 4
4.7.3 Setting the Auxiliary Output
Switch 5 on the DIP switch determines how the auxiliary power operates on the 5395.
The 5395 checks switch 5 only when powering up the 5395. If you change this switch, you must
remove both the AC power and the battery to force the 5395 to recognize the new switch setting.
12
3
5
4
12
3 54
OFFON
dips5
Figure 4-9. Setting DIP Switch 5