Installation manual
Model 5395 Distributed Power Module
18 150933 / Rev. 9/96
*Switch1,3ON
Switch2OFF
* See the following information about ANSI temporal-coded outputs
Switch1ON
Switch 2-3 OFF
12
3
4
5
12
3
45
Switch 1-2 ON
Switch3OFF
12
3
45
Switch 1-3
ON
12
3
45
dips
Figure 4-7. Setting DIP Switches 1-3
Special Note for Input/Output Configurations That Select ANSI Temporal-Coded Outputs
The DIP switch settings marked with an asterisk (*) in Figure 4-7 are designed to produce ANSI
temporal-coded outputs from a constant on input. The figures shown below compare the output
patterns of configurations before and after the addition of this feature.
Input
Output
Input
Output
4sec.
.5 sec. on, .5 sec. off, .5 sec. on, .5 sec. off, .5 sec. on, 1.5 sec. off
(repeat)
Standard 5395 Input to Output Relationship Input/Output Relationship for ANSI
Temporal-coded Options
With this new feature, a steady signal can produce the pattern shown above for panels not
previously able to do so.
Note: The 5395 can also produce other temporal patterns if the patterns appear at the inputs for
the non-ANSI temporal configurations.